489 GENERATOR MANAGEMENT RELAY – COMMUNICATIONS GUIDE
65
• A Status of “Control Operation not Supported for this Point” (4) will be returned if an
attempt was made to operate the point and the relay, owing to its configuration,
does not allow the point to perform its function.
An operate of the Reset point may fail (even if the command is accepted) due to other
inputs or conditions (e.g., blocks) existing at the time. To verify the success or failure of an
operate of this point it is necessary that the associated Binary Input(s) be examined after
the control attempt is performed.
When using object 10 to read the status of any Binary Output, a value of zero will always
be returned. This is due to the fact that all points are “Pulse On” and are deemed to be
normally off.
CG.5.3 Binary / Frozen Counter (Objects 20/21)
Table CG–7: Counters Point List
INDEX
ROLLOVER
POINT
DESCRIPTION
0
50000
Number of Breaker Operations
1
50000
Number of Thermal Resets
2
50000
Number of Trips (total)
3
50000
Number of Digital Input Trips
4
50000
Number of Sequential Trips
5
50000
Number of Field-Breaker Discrepancy Trips
6
50000
Number of Tachometer Trips
7
50000
Number of Offline Overcurrent Trips
8
50000
Number of Phase Overcurrent Trips
9
50000
Number of Negative Sequence Overcurrent Trips
10
50000
Number of Ground Overcurrent Trips
11
50000
Number of Phase Differential Trips
12
50000
Number of Undervoltage Trips
13
50000
Number of Overvoltage Trips
14
50000
Number of Volts/Hertz Trips
15
50000
Number of Phase Reversal Trips
16
50000
Number of Underfrequency Trips
17
50000
Number of Overfrequency Trips
18
50000
Number of Neutral Overvoltage (Fundamental) Trips
19
50000
Number of Neutral Undervoltage (Third Harmonic) Trips