44
489 GENERATOR MANAGEMENT RELAY – COMMUNICATIONS GUIDE
F22
16 bits
TWO 8-BIT CHARACTERS
PACKED INTO 16-BIT UNSIGNED
MSB
First Character
LSB
Second Character
Example: String ‘AB’ stored as 4142 hex.
F24
32 bits
TIME FORMAT FOR BROADCAST
1
st
byte
Hours (0 to 23)
2
nd
byte
Minutes (0 to 59)
3
rd
& 4
th
bytes
Milliseconds (0 to 59999)
Note: Clock resolution limited to 0.01 sec
Example: 1:15:48:572 stored as 17808828 (i.e., 1
st
word 010F, 2
nd
word
BDBC)
F50
16 bits
ASSIGN ALARM/TRIP RELAYS
Bit 0
Relay 1
Bit 1
Relay 2
Bit 2
Relay 3
Bit 3
Relay 4
Bit 4
Relay 5
Bits 5 to 15
Not used
F100
Unsigned
16 bit integer
TEMPERATURE DISPLAY UNITS
0
Celsius
1
Fahrenheit
F101
Unsigned
16 bit integer
RS485 BAUD RATE
0
300 baud
1
1200 baud
2
2400 baud
3
4800 baud
4
9600 baud
5
19200 baud
F102
Unsigned
16 bit integer
RS485 PARITY
0
None
1
Odd
2
Even
F103
Unsigned
16 bit integer
NO/YES SELECTION
0
No
1
Yes
F104
Unsigned
16 bit integer
GROUND CT TYPE
0
None
1
1 A Secondary
2
50/0.025 Ground CT
3
5 A Secondary
F105
Unsigned
16 bit integer
OFF/ON SELECTION
0
Off
1
On
F106
Unsigned
16 bit integer
VOLTAGE TRANSFORMER CONNECTION TYPE
0
None
1
Open Delta
2
Wye
Table CG–2: Data Formats (Sheet 3 of 14)