489 GENERATOR MANAGEMENT RELAY – COMMUNICATIONS GUIDE
35
26E7
Assign Trip Relays (1-4)
0 to 3
1
–
F50
1
26E8
RTD #12 Trip Temperature
1 to 250
1
°C
F1
80
26E9
RTD #12 Name
0 to 8
1
–
F22
_
RTD TEMPERATURE / OPEN RTD SENSOR
2720
Open RTD Sensor Alarm
0 to 2
1
–
F115
0
2721
Assign Alarm Relays (2-5)
1 to 4
1
–
F50
16
2722
Open RTD Sensor Alarm Events
0 to 1
1
–
F105
0
RTD TEMPERATURE / RTD SHORT/LOW TEMPERATURE
2740
RTD Short/Low Temperature Alarm
0 to 2
1
–
F115
0
2741
Assign Alarm Relays (2-5)
1 to 4
1
–
F50
16
2742
RTD Short/Low Temperature Alarm Events
0 to 1
1
–
F105
0
THERMAL MODEL / MODEL SETUP
2800
Enable Thermal Model
0 to 1
1
–
F103
0
2801
Overload Pickup Level
101 to 125
1
×
FLA
F3
101
2802
Unbalance Bias K Factor
0 to 12
1
–
F1
0
2803
Cool Time Constant Online
0 to 500
1
min
F1
15
2804
Cool Time Constant Offline
0 to 500
1
min
F1
30
2805
Hot/Cold Safe Stall Ratio
1 to 100
1
–
F3
100
2806
Enable RTD Biasing
0 to 1
1
–
F103
0
2807
RTD Bias Minimum
0 to 250
1
°C
F1
40
2808
RTD Bias Center Point
0 to 250
1
°C
F1
130
2809
RTD Bias Maximum
0 to 250
1
°C
F1
155
280A
Select Curve Style
0 to 2
1
–
F142
0
280B
Standard Overload Curve Number
1 to 15
1
–
F1
4
280C
Time to Trip at 1.01
×
FLA
5 to 999999
1
s
F10
5
280E
Time to Trip at 1.05
×
FLA
5 to 999999
1
s
F10
5
2810
Time to Trip at 1.10
×
FLA
5 to 999999
1
s
F10
5
2812
Time to Trip at 1.20
×
FLA
5 to 999999
1
s
F10
5
2814
Time to Trip at 1.30
×
FLA
5 to 999999
1
s
F10
5
2816
Time to Trip at 1.40
×
FLA
5 to 999999
1
s
F10
5
2818
Time to Trip at 1.50
×
FLA
5 to 999999
1
s
F10
5
281A
Time to Trip at 1.75
×
FLA
5 to 999999
1
s
F10
5
281C
Time to Trip at 2.00
×
FLA
5 to 999999
1
s
F10
5
281E
Time to Trip at 2.25
×
FLA
5 to 999999
1
s
F10
5
2820
Time to Trip at 2.50
×
FLA
5 to 999999
1
s
F10
5
2822
Time to Trip at 2.75
×
FLA
5 to 999999
1
s
F10
5
2824
Time to Trip at 3.00
×
FLA
5 to 999999
1
s
F10
5
2826
Time to Trip at 3.25
×
FLA
5 to 999999
1
s
F10
5
2828
Time to Trip at 3.50
×
FLA
5 to 999999
1
s
F10
5
282A
Time to Trip at 3.75
×
FLA
5 to 999999
1
s
F10
5
282C
Time to Trip at 4.00
×
FLA
5 to 999999
1
s
F10
5
282E
Time to Trip at 4.25
×
FLA
5 to 999999
1
s
F10
5
2830
Time to Trip at 4.50
×
FLA
5 to 999999
1
s
F10
5
2832
Time to Trip at 4.75
×
FLA
5 to 999999
1
s
F10
5
2834
Time to Trip at 5.00
×
FLA
5 to 999999
1
s
F10
5
2836
Time to Trip at 5.50
×
FLA
5 to 999999
1
s
F10
5
2838
Time to Trip at 6.00
×
FLA
5 to 999999
1
s
F10
5
283A
Time to Trip at 6.50
×
FLA
5 to 999999
1
s
F10
5
283C
Time to Trip at 7.00
×
FLA
5 to 999999
1
s
F10
5
283E
Time to Trip at 7.50
×
FLA
5 to 999999
1
s
F10
5
2840
Time to Trip at 8.00
×
FLA
5 to 999999
1
s
F10
5
2842
Time to Trip at 10.0
×
FLA
5 to 999999
1
s
F10
5
2844
Time to Trip at 15.0
×
FLA
5 to 999999
1
s
F10
5
Table CG–1: 489 Memory Map (Sheet 23 of 30)