489 GENERATOR MANAGEMENT RELAY – COMMUNICATIONS GUIDE
31
20CA
Neutral Overvoltage Curve Reset Rate
0 to 9999
1
s
F2
0
20CB
Neutral Overvoltage Trip Element
0 to 1
1
–
F208
1
VOLTAGE ELEMENTS / NEUTRAL UNDERVOLTAGE (3rd HARMONIC)
20E0
Low Power Blocking Level
2 to 99
1
×
Rated MW
F14
5
20E2
Low Voltage Blocking Level
50 to 100
1
×
Rated
F3
75
20E3
Neutral Undervoltage Alarm
0 to 2
1
–
F115
0
20E4
Assign Alarm Relays (2-5)
1 to 4
1
–
F50
16
20E5
Neutral Undervoltage Alarm Level
5 to 200
1
V
F2
5
20E6
Neutral Undervoltage Alarm Delay
5 to 120
1
s
F1
30
20E7
Neutral Undervoltage Alarm Events
0 to 1
1
–
F105
0
20E8
Neutral Undervoltage Trip
0 to 2
1
–
F115
0
20E9
Assign Trip Relays (1-4)
0 to 3
1
–
F50
1
20EA
Neutral Undervoltage Trip Level
5 to 200
1
V
F2
10
20EB
Neutral Undervoltage Trip Delay
5 to 120
1
s
F1
30
VOLTAGE ELEMENTS / LOSS OF EXCITATION
2100
Enable Voltage Supervision
0 to 1
1
–
F103
0
2101
Voltage Level
70 to 100
1
×
rated
F3
70
2102
Circle 1 Trip
0 to 2
1
–
F115
0
2103
Assign Circle 1 Trip Relays (1-4)
0 to 3
1
–
F50
1
2104
Circle 1 Diameter
25 to 3000
1
Ω
s
F2
250
2105
Circle 1 Offset
10 to 3000
1
Ω
s
F2
25
2106
Circle 1 Trip Delay
1 to 100
1
s
F2
50
2107
Circle 2 Trip
0 to 2
1
–
F115
0
2108
Assign Circle 2 Trip Relays (1-4)
0 to 3
1
–
F50
1
2109
Circle 2 Diameter
25 to 3000
1
Ω
s
F2
350
210A
Circle 2 Offset
10 to 3000
1
Ω
s
F2
25
210B
Circle 2 Trip Delay
1 to 100
1
s
F2
50
VOLTAGE ELEMENTS / DISTANCE ELEMENT
2130
Step Up Transformer Setup
0 to 1
1
–
F219
0
2131
Fuse Failure Supervision
0 to 1
1
–
F105
0
2132
Zone 1 Trip
0 to 2
1
–
F115
0
2133
Assign Zone 1 Trip Relays (1-4)
0 to 3
1
–
F50
1
2134
Zone 1 Reach
1 to 5000
1
Ω
s
F2
100
2135
Zone 1 Angle
50 to 85
1
°
F1
75
2136
Zone 1 Trip Delay
0 to 1500
1
s
F2
4
2137
Zone 2 Trip
0 to 2
1
–
F115
0
2138
Assign Zone 2 Trip Relays (1-4)
0 to 3
1
–
F50
1
2139
Zone 2 Reach
1 to 5000
1
Ω
s
F2
100
213A
Zone 2 Angle
50 to 85
1
°
F1
75
213B
Zone 2 Trip Delay
0 to 1500
1
s
F2
20
POWER ELEMENTS / REACTIVE POWER
2200
Block Mvar Element From Online
0 to 5000
1
s
F1
1
2201
Reactive Power Alarm
0 to 2
1
–
F115
0
2202
Assign Alarm Relays (2-5)
1 to 4
1
–
F50
16
2203
Positive Mvar Alarm Level
2 to 201
1
x rated
F14
85
2205
Negative Mvar Alarm Level
3
2 to 201
1
x rated
F14
85
2207
Negative Mvar Alarm Delay
2 to 1200
1
s
F2
10
2208
Reactive Power Alarm Events
0 to 1
1
–
F105
0
2209
Reactive Power Trip
0 to 2
1
–
F115
0
220A
Assign Trip Relays (1-4)
0 to 3
1
–
F50
1
220B
Positive Mvar Trip Level
3
2 to 201
1
Mvar
F14
80
220D
Negative Mvar Trip Level
3
2 to 201
1
Mvar
F14
80
Table CG–1: 489 Memory Map (Sheet 19 of 30)
ADDR
Name
RANGE
STEP
UNITS
FORMAT
DEFAULT
1, 2, 3
See Table footnotes on page page 42