489 GENERATOR MANAGEMENT RELAY – COMMUNICATIONS GUIDE
21
1006
Passcode (Write Only)
0 to 99999999
1
N/A
F12
0
1008
Encrypted Passcode (Read Only)
Note: From version 4.06 onward, relay
response to read request is 00000000.
N/A
N/A
N/A
F12
N/A
100A
Waveform Memory Buffer
1 to 16
1
–
F1
8
489 SETUP / SERIAL PORTS
1010
Slave Address
1 to 254
1
–
F1
254
1011
Computer RS485 Baud Rate
0 to 5
1
–
F101
4
1012
Computer RS485 Parity
0 to 2
1
–
F102
0
1013
Auxiliary RS485 Baud Rate
0 to 5
1
–
F101
4
1014
Auxiliary RS485 Parity
0 to 2
1
–
F102
0
1015
Port Used For DNP
0 to 3
1
–
F216
0
1016
DNP Slave Address
0 to 255
1
–
F1
255
1017
DNP Turnaround Time
0 to 100
10
ms
F1
10
COMMUNICATION SETPOINTS
1020
Ethernet IP address
---
---
---
F150
0
1022
Ethernet subnet mask
---
---
--–
F150
FFFFFC00
1024
Ethernet gateway address
---
---
--–
F150
0
102C
Front RS232 baud rate
0 to 5
1
---
F101
5
489 SETUP / REAL TIME CLOCK
1030
Date
N/A
N/A
N/A
F18
N/A
1032
Time
N/A
N/A
N/A
F19
N/A
1034
IRIG-B Type
0 to 2
1
–
F220
0
489 SETUP / MESSAGE SCRATCHPAD
1060
Scratchpad
0 to 40
1
–
F22
_
1080
Scratchpad
0 to 40
1
–
F22
_
10A0
Scratchpad
0 to 40
1
–
F22
_
10C0
Scratchpad
0 to 40
1
–
F22
_
10E0
Scratchpad
0 to 40
1
–
F22
_
489 SETUP / CLEAR DATA
1130
Clear Last Trip Data
0 to 1
1
–
F103
0
1131
Clear Mwh And Mvarh Meters
0 to 1
1
–
F103
0
1132
Clear Peak Demand Data
0 to 1
1
–
F103
0
1133
Clear RTD Maximums
0 to 1
1
–
F103
0
1134
Clear Analog Inputs Minimums/Maximums
0 to 1
1
–
F103
0
1135
Clear Trip Counters
0 to 1
1
–
F103
0
1136
Clear Event Record
0 to 1
1
–
F103
0
1137
Clear Generator Information
0 to 1
1
–
F103
0
1138
Clear Breaker Information
0 to 1
1
–
F103
0
SYSTEM SETUP / CURRENT SENSING
1180
Phase CT Primary
10 to 50001
1
Amps
F1
50001
1181
Ground CT
0 to 3
1
–
F104
0
1182
Ground CT Ratio
5 to 10000
1
: 1 / :5
F1
100
SYSTEM SETUP / VOLTAGE SENSING
11A0
VT Connection Type
0 to 2
1
–
F106
0
11A1
Voltage Transformer Ratio
100 to 30000
1
: 1
F3
500
11A2
Neutral VT Ratio
100 to 24000
1
: 1
F3
500
11A3
Neutral Voltage Transformer
0 to 1
1
–
F103
0
SYSTEM SETUP / GEN. PARAMETERS
11C0
Generator Rated MVA
50 to 2000001
1
MVA
F13
2000001
11C2
Generator Rated Power Factor
5 to 100
1
–
F3
100
11C3
Generator Voltage Phase-Phase
100 to 30001
1
V
F1
30001
11C4
Generator Nominal Frequency
0 to 3
1
Hz
F107
0
Table CG–1: 489 Memory Map (Sheet 9 of 30)
ADDR
Name
RANGE
STEP
UNITS
FORMAT
DEFAULT
1, 2, 3
See Table footnotes on page page 42