30
489 GENERATOR MANAGEMENT RELAY – COMMUNICATIONS GUIDE
2040
Volts/Hertz Alarm
0 to 2
1
–
F115
0
2041
Assign Alarm Relays (2-5)
1 to 4
1
–
F50
16
2042
Volts/Hertz Alarm Pickup
50 to 199
1
×
Nominal
F3
100
2043
Volts/Hertz Alarm Delay
1 to 1500
1
s
F2
30
2044
Volts/Hertz Alarm Events
0 to 1
1
–
F105
0
2045
Volts/Hertz Trip
0 to 2
1
–
F115
0
2046
Assign Trip Relays (1-4)
0 to 3
1
–
F50
1
2047
Volts/Hertz Trip Pickup
50 to 199
1
×
Nominal
F3
100
2048
Volts/Hertz Trip Delay
1 to 1500
1
s
F2
10
2049
Volts/Hertz Curve Reset Rate
0 to 9999
1
s
F2
14
204A
Volts/Hertz Trip Element
0 to 3
1
–
F211
0
VOLTAGE ELEMENTS / PHASE REVERSAL
2060
Phase Reversal Trip
0 to 2
1
–
F115
0
2061
Assign Trip Relays (1-4)
0 to 3
1
–
F50
1
VOLTAGE ELEMENTS / UNDERFREQUENCY
2080
Block Underfrequency From Online
0 to 5
1
s
F1
1
2081
Voltage Level Cutoff
50 to 99
1
×
Rated
F3
50
2082
Underfrequency Alarm
0 to 2
1
–
F115
0
2083
Assign Alarm Relays (2-5)
1 to 4
1
–
F50
16
2084
Underfrequency Alarm Level
2000 to 6000
1
Hz
F3
5950
2085
Underfrequency Alarm Delay
1 to 50000
1
s
F2
50
2086
Underfrequency Alarm Events
0 to 1
1
–
F105
0
2087
Underfrequency Trip
0 to 2
1
–
F115
0
2088
Assign Trip Relays (1-4)
0 to 3
1
–
F50
1
2089
Underfrequency Trip Level 1
2000 to 6000
1
Hz
F3
5950
208A
Underfrequency Trip Delay 1
1 to 50000
1
s
F2
600
208B
Underfrequency Trip Level 2
2000 to 6000
1
Hz
F3
5800
208C
Underfrequency Trip Delay 2
1 to 50000
1
s
F2
300
VOLTAGE ELEMENTS / OVERFREQUENCY
20A0
Block Overfrequency From Online
0 to 5
1
s
F1
1
20A1
Voltage Level Cutoff
50 to 99
1
×
Rated
F3
50
20A2
Overfrequency Alarm
0 to 2
1
–
F115
0
20A3
Assign Alarm Relays (2-5)
1 to 4
1
–
F50
16
20A4
Overfrequency Alarm Level
2501 to 7000
1
Hz
F3
6050
20A5
Overfrequency Alarm Delay
1 to 50000
1
s
F2
50
20A6
Overfrequency Alarm Events
0 to 1
1
–
F105
0
20A7
Overfrequency Trip
0 to 2
1
–
F115
0
20A8
Assign Trip Relays (1-4)
0 to 3
1
–
F50
1
20A9
Overfrequency Trip Level 1
2501 to 7000
1
Hz
F3
6050
20AA
Overfrequency Trip Delay 1
1 to 50000
1
s
F2
600
20AB
Overfrequency Trip Level 2
2501 to 7000
1
Hz
F3
6200
20AC
Overfrequency Trip Delay 2
1 to 50000
1
s
F2
300
VOLTAGE ELEMENTS / NEUTRAL OVERVOLTAGE (FUNDAMENTAL)
20C0
Neutral Overvoltage Alarm
0 to 2
1
–
F115
0
20C1
Assign Alarm Relays (2-5)
1 to 4
1
–
F50
16
20C2
Neutral Overvoltage Alarm Level
20 to 1000
1
Vsec
F2
30
20C3
Neutral Overvoltage Alarm Delay
1 to 1200
1
s
F2
10
20C4
Neutral Overvoltage Alarm Events
0 to 1
1
–
F105
0
20C5
Neutral Overvoltage Trip
0 to 2
1
–
F115
0
20C6
Assign Trip Relays (1-4)
0 to 3
1
–
F50
1
20C7
Neutral Overvoltage Trip Level
20 to 1000
1
Vsec
F2
50
20C8
Neutral Overvoltage Trip Delay
1 to 1200
1
s
F2
10
20C9
Supervise With Digital Input
0 to 1
1
–
F103
0
Table CG–1: 489 Memory Map (Sheet 18 of 30)