40
489 GENERATOR MANAGEMENT RELAY – COMMUNICATIONS GUIDE
2C93
Analog Input 3 Alarm Events
0 to 1
1
–
F105
0
2C94
Analog Input 3 Trip
0 to 2
1
–
F115
0
2C95
Assign Trip Relays (1-4)
0 to 3
1
–
F50
1
2C96
Analog Input 3 Trip Level
–50000 to 50000
1
Units
F12
20
2C98
Analog Input 3 Trip Pickup
0 to 1
1
–
F130
0
2C99
Analog Input 3 Trip Delay
1 to 3000
1
s
F2
1
2C9A
Analog Input 3 Name
0 to 12
1
–
F22
_
ANALOG INPUT/OUTPUT / ANALOG INPUT 4
2CC0
Analog Input 4
0 to 3
1
–
F129
0
2CC5
Analog Input 4 Units
0 to 6
1
–
F22
_
2CC8
Analog Input 4 Minimum
–50000 to 50000
1
Units
F12
0
2CCA
Analog Input 4 Maximum
–50000 to 50000
1
Units
F12
100
2CCC
Block Analog Input 4 From Online
0 to 5000
1
s
F1
0
2CCD
Analog Input 4 Alarm
0 to 2
1
–
F115
0
2CCE
Assign Alarm Relays (2-5)
1 to 4
1
–
F50
16
2CCF
Analog Input 4 Alarm Level
–50000 to 50000
1
Units
F12
10
2CD1
Analog Input 4 Alarm Pickup
0 to 1
1
–
F130
0
2CD2
Analog Input 4 Alarm Delay
1 to 3000
1
s
F2
1
2CD3
Analog Input 4 Alarm Events
0 to 1
1
–
F105
0
2CD4
Analog Input 4 Trip
0 to 2
1
–
F115
0
2CD5
Assign Trip Relays (1-4)
0 to 3
1
–
F50
1
2CD6
Analog Input 4 Trip Level
–50000 to 50000
1
Units
F12
20
2CD8
Analog Input 4 Trip Pickup
0 to 1
1
–
F130
0
2CD9
Analog Input 4 Trip Delay
1 to 3000
1
s
F2
1
2CDA
Analog Input 4 Name
0 to 12
1
–
F22
_
489 TESTING / SIMULATION MODE
2D00
Simulation Mode
0 to 3
1
–
F138
0
2D01
Pre-fault To Fault Time Delay
0 to 300
1
s
F1
15
489 TESTING / PRE-FAULT SETUP
2D20
Pre-Fault Iphase Output
0 to 2000
1
×
CT
F3
0
2D21
Pre-Fault Voltages Phase-N
0 to 150
1
×
Rated
F3
100
2D22
Pre-Fault Current Lags Voltage
0 to 359
1
°
F1
0
2D23
Pre-Fault Iphase Neutral
0 to 2000
1
×
CT
F3
0
2D24
Pre-Fault Current Ground
0 to 2000
1
×
CT
F3
0
2D25
Pre-Fault Voltage Neutral
0 to 1000
1
Volts
F2
0
2D26
Pre-Fault Stator RTD Temp
–50 to 250
1
°C
F4
40
2D27
Pre-Fault Bearing RTD Temp
–50 to 250
1
°C
F4
40
2D28
Pre-Fault Other RTD Temp
–50 to 250
1
°C
F4
40
2D29
Pre-Fault Ambient RTD Temp
–50 to 250
1
°C
F4
40
2D2A
Pre-Fault System Frequency
50 to 900
1
Hz
F2
600
2D2B
Pre-Fault Analog Input 1
0 to 100
1
%
F1
0
2D2C
Pre-Fault Analog Input 2
0 to 100
1
%
F1
0
2D2D
Pre-Fault Analog Input 3
0 to 100
1
%
F1
0
2D2E
Pre-Fault Analog Input 4
0 to 100
1
%
F1
0
2D4C
Pre-Fault Stator RTD Temp
–50 to 250
1
°F
F4
40
2D4D
Pre-Fault Bearing RTD Temp
–50 to 250
1
°F
F4
40
2D4E
Pre-Fault Other RTD Temp
–50 to 250
1
°F
F4
40
2D4F
Pre-Fault Ambient RTD Temp
–50 to 250
1
°F
F4
40
489 TESTING / FAULT SETUP
2D80
Fault Iphase Output
0 to 2000
1
×
CT
F3
0
2D81
Fault Voltages Phase-N
0 to 150
1
×
Rated
F3
100
2D82
Fault Current Lags Voltage
0 to 359
1
°
F1
0
2D83
Fault Iphase Neutral
0 to 2000
1
×
CT
F3
0
Table CG–1: 489 Memory Map (Sheet 28 of 30)
ADDR
Name
RANGE
STEP
UNITS
FORMAT
DEFAULT
1, 2, 3
See Table footnotes on page page 42