BHGE
ADVANCED (118)
Any
Advanced/Standard implementation for the device
BLOCK_ERR_DESC_1
(119)
Bit map; bit N = 0 - No error, bit N = 1 - Specific error
occurred.
Bit 0: No Error. Reserved. Must be always 0.
Bit 1: Mode Switch Error. 1 = The PTB Actual mode cannot
be set to any non-AUTO mode.
Bit 2: The response to the FF request times out.
Bit 3: SP Source conflict. 1 = A DO block attempts to
become a SP source on the channel already taken by the
other DO block.
Bit 4: FIND_STOPS Failed. 1 = Find Stops request made by
writing FIND_STOPS parameter failed.
Table 31 Transducer Block Parameters (Continued)
Parameter (in bold)
Sub-parameter (Index)
Range
Initial
Value
Mode
Description