© 2019 Baker Hughes, a GE company, LLC. All rights reserved.
24
|
BHGE
Physical and Operational Description
The SVI FF is housed in an industrial, tough, weatherproof, corrosion resistant aluminum
housing that has been designed for operation in hazardous areas as listed in Appendix B.
Electrical connections are made through two 1/2" NPT conduit entries. Pneumatic connections
are made through two or three ¼" NPT ports.
Electronics Module
The Electronics module consists of an electronic circuit encapsulated in a housing. The
electronics include a multiplexer, A/D, D/A, temperature sensor, Hall-Effect magnetic position
sensor, pressure sensors, a micro controller, and a power management/distribution circuit.
The programs controlling the SVI FF digital valve positioner are stored in a flash memory that
allows for the downloading of upgraded firmware.
A separate non-volatile memory stores configuration information, and continuous diagnostic
results. Expansion capabilities include connectors for the addition of the optional local display
with pushbuttons. Using the internal programmed positioner algorithm, the CPU computes
the required output based on information received from the measurement sensors. The base
module has no user repairable components.
Magnetic Position Sensor
A non-contact sensor uses a magnetic field to transfer the position through the wall of the
housing, without penetration, to sense the valve position. A Hall effect device, sealed within
the electronics housing, senses the rotation of a magnetic assembly mounted on the end of a
rotary valve shaft or on a driven linkage mounted on a reciprocating valve.
The output of the Hall sensor provides the position feedback signal to the position control
algorithm. The magnetic assembly is environmentally sealed and is entirely external to the
electronics housing (See Figure 26 on page 57). The Hall effect sensor has a maximum travel
range of up to 140° rotation.
Position Display
The position sensor also provides, through the electronics module, a readout of valve position
on the optional display and communication of valve position via FF protocol.
Pressure Sensor
The pressure sensor located in the Electronics Module measures the output of the single
acting relay. The pressure measurement is displayed on the local display or read by an FF
communication device.
Содержание Baker Hughes Masoneilan SVI FF
Страница 12: ...This page intentionally left blank ...
Страница 72: ...This page intentionally left blank ...
Страница 82: ...This page intentionally left blank ...
Страница 94: ...This page intentionally left blank ...
Страница 108: ...This page intentionally left blank ...
Страница 198: ...This page intentionally left blank ...
Страница 206: ...This page intentionally left blank ...
Страница 224: ...This page intentionally left blank ...
Страница 228: ...This page intentionally left blank ...
Страница 230: ...This page intentionally left blank ...
Страница 250: ...This page intentionally left blank ...
Страница 262: ...This page intentionally left blank ...
Страница 263: ......