Switch Settings
The discrete output switch can be opened or closed in response to conditions that the SVI FF
detects. This action is defined via DISCRETE_SWITCH_1_CONF (
Discrete Switch 1
on the SVI FF
software) and are:
0.
Disabled
- the switch is always inactive (default).
1.
DO Block
- the switch’s state is linked to the state of a DO block. If the
DO block feedback configuration changes, then the switch changes
state. The DO switch auto-detects which DO block has the matching
CHANNEL and translates 0 to inactive and non-0 to active. This is
configured using the
Software Switches
tab on the DTM or using the
DD.
2.
Fault State
- the switch is activated whenever a fault occurs and the
switch remains activated until the SVI FF status is cleared.
3.
Not in Normal
- the switch is activated whenever the mode in not
Normal.
4.
Maintenance Required
- the switch is activated whenever the device
has an alert that requires maintenance.
5.
Warning Data
- the switch is activated whenever the TB block error
Warning Data
bit is set. This is manifested as a maintenance needed
soon indication.
6.
Air Supply Alert
- the switch is activated whenever there is an air sup-
ply alert. This is configured using the
Pressure Alarms
tabs on the
DTM or using the DD.
7.
Travel Deviation Alert
- the switch is activated whenever a travel
deviation alert occurs. This is configured using the
Travel Alarms
tabs
on the DTM or using the DD.
8.
Position HI Alert
- the switch is activated whenever a user-configured
Position HI
alert setting is exceeded. This is configured using the
Posi-
tion Alarms
tabs on the DTM or using the DD.
9.
Position LO Alert
- the switch is activated whenever a user-config-
ured
Position LO
alert setting is exceeded. This is configured using
the
Position Alarms
tabs on the DTM or using the DD.
10.
Always Active
- the switch is always active and does not change
state.
The directional state of the switch is set using the
Software Switches
tab or using the DD’s
DISCRETE_SWITCH_1_CONF.DIRECTION
.
NOTE
Содержание Baker Hughes Masoneilan SVI FF
Страница 12: ...This page intentionally left blank ...
Страница 72: ...This page intentionally left blank ...
Страница 82: ...This page intentionally left blank ...
Страница 94: ...This page intentionally left blank ...
Страница 108: ...This page intentionally left blank ...
Страница 198: ...This page intentionally left blank ...
Страница 206: ...This page intentionally left blank ...
Страница 224: ...This page intentionally left blank ...
Страница 228: ...This page intentionally left blank ...
Страница 230: ...This page intentionally left blank ...
Страница 250: ...This page intentionally left blank ...
Страница 262: ...This page intentionally left blank ...
Страница 263: ......