© 2019 Baker Hughes, a GE company, LLC. All rights reserved.
160
|
BHGE
TRAVEL_
ACCUMULATION (1)
0
Totalized change in travel, since the TRAVEL_ACCUMULA-
TION was cleared. The value increments when the magni-
tude of the change exceeds the DEADBAND.
Not writable for Standard Diagnostics version.
ALERT_POINT (2)
0-0xFFFF
FFFF
1Milion
Travel accumulation value, above which the ALERT is set
to True.
Not writable for Standard Diagnostics version.
DEADBAND_
AB (3)
0.1-10
1
POSITION change, required to exceed, before the TRAVEL
ACCUMULATION is increased.
Not writable for Standard Diagnostics version.
ALERT (4)
0
0
True if the TRAVEL_ACCUMULATION is above
ALERT_POINT.
Not writable for Standard Diagnostics version.
HISTORIC ALERT (5)
0
0
True if ALERT is true.
Not Changed if ALERT is false.
Not writable for Standard Diagnostics version.
ENABLE (6)
0
TRUE
True - Enables the ALERT
to be reported according to the
configuration.
False - Disables ALERT
reporting.
Not writable for Standard Diagnostics version.
TRAVEL_
ACCUMULATION_
TREND (33)
The total change in travel trend. The value increments
when the magnitude of the change exceeds the TRAV-
EL_ACCUMULATION_ALERT.DEADBAND.
No value for Standard Diagnostics version.
CURRENTLY
COLLECTED (1)
0
Travel accumulation for the current 24 hours period.
No value for Standard Diagnostics version.
TODAY(FULL DAY) (2)
0
Travel accumulation for the last full 24 hours period.
No value for Standard Diagnostics version.
LAST_DAY (3)
0
Travel accumulation for the previous full 24 hours period.
No value for Standard Diagnostics version.
PREVIOUS_DAY (4)
0
Travel accumulation for the previous full 24 hours period.
No value for Standard Diagnostics version.
THREE_DAYS_AGO (5)
0
Travel accumulation for the last three days current week.
No value for Standard Diagnostics version.
CURRENT_WEEK (6)
0
Travel accumulation for the current week.
No value for Standard Diagnostics version.
LAST_WEEK (7)
0
Travel accumulation for the last full week.
No value for Standard Diagnostics version.
Table 31 Transducer Block Parameters (Continued)
Parameter (in bold)
Sub-parameter (Index)
Range
Initial
Value
Mode
Description
Содержание Baker Hughes Masoneilan SVI FF
Страница 12: ...This page intentionally left blank ...
Страница 72: ...This page intentionally left blank ...
Страница 82: ...This page intentionally left blank ...
Страница 94: ...This page intentionally left blank ...
Страница 108: ...This page intentionally left blank ...
Страница 198: ...This page intentionally left blank ...
Страница 206: ...This page intentionally left blank ...
Страница 224: ...This page intentionally left blank ...
Страница 228: ...This page intentionally left blank ...
Страница 230: ...This page intentionally left blank ...
Страница 250: ...This page intentionally left blank ...
Страница 262: ...This page intentionally left blank ...
Страница 263: ......