Mins and Maxs
A set of parameters are provided in the Transducer block to register the maximum and
minimum value of most dynamic parameters. The extreme values are cleared if the valve is
rebooted. Table 35 though Table 38 provides the values being monitored in various areas.
* These two values are useful in determining calibration error: Whether or not the valve is
operating at near 105% or near -5%.
The items in these tables can be used as constructive guidelines
for alert configuration.
Table 35 Valve Position Values Monitored
114-POSITION_EXTREMES
DESCRIPTION
1
FINAL_VALUE_MAX
Max value of Position Setpoint
2
FINAL_VALUE_MIN
Min value of Position Setpoint
3
FINAL_POS_VALUE_MAX*
Max value of Actual Position: Represents a possible calibration issue
if the position is above 100% when the valve is fully open.
4
FINAL_POS_VALUE_MIN*
Min value of Actual Position: Represents a possible calibration issue if
the position is below 0% when the valve is fully closed.
5
WORKING_SP_MAX
Max value of Characterized Position Setpoint
6
WORKING_SP_MIN
Min value of Characterized Position Setpoint
7
WORKING_POS_MAX
Max value of Characterized Actual Position
8
WORKING_POS_MIN
Min value of Characterized Actual Position
NOTE
Содержание Baker Hughes Masoneilan SVI FF
Страница 12: ...This page intentionally left blank ...
Страница 72: ...This page intentionally left blank ...
Страница 82: ...This page intentionally left blank ...
Страница 94: ...This page intentionally left blank ...
Страница 108: ...This page intentionally left blank ...
Страница 198: ...This page intentionally left blank ...
Страница 206: ...This page intentionally left blank ...
Страница 224: ...This page intentionally left blank ...
Страница 228: ...This page intentionally left blank ...
Страница 230: ...This page intentionally left blank ...
Страница 250: ...This page intentionally left blank ...
Страница 262: ...This page intentionally left blank ...
Страница 263: ......