The window on the right side presents the Network management parameters and their
values.
3. Edit the values to match the default/recommended settings by the FOUNDATION fieldbus
in document
FF-940 FS 1.5 - Communication Profile
chapter
5.4 Default link settings for
communication parameters on H1_31_25kbps Physical Layer networks
.
4. Click
OK
to accept the settings and close the window (Figure 74).
Figure 74 Network Management Parameter List
5. Ensure that the modified values are downloaded to the controller by selecting
Files ->
Download
.
E. Setting the Positioner’s Address
To speed up the process of device discovery, reduce the working address range. If it is an
existing application with multiple devices connected, you can find the devices and their
addresses when you click on the segment and select
Device List
Figure 75 Device List