![background image](http://html1.mh-extra.com/html/ge-multilin/850/850_communications-manual_3949189272.webp)
13-150
8 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE
CHAPTER 13: MODBUS MEMORY MAP
53432
0x3477 Point 95
0
0xC6CD00
1
FC142
0
2
Y Y Y Y
53434
0x3479 Present in Gen
Interrogation
0
1
1
FC126B 0
1
Y Y Y Y
First ASDU
53460
0x3493 First ASDU Ident Type
0
1
1
FC212
0
1
Y Y Y Y
53461
0x3494 First ASDU Func Type
0
255
1
F0
0
1
Y Y Y Y
53462
0x3495 First ASDU Info Num
0
255
1
F0
0
1
Y Y Y Y
53463
0x3496 First ASDU Scan Timeout 0
1000
1
s
F0
0
1
Y Y Y Y
53464
0x3497 First Analog Entry
0
36807
1
FC273
0
1
Y Y Y Y
53465
0x3498 First Analog Factor
0
65535
1
F3
0
1
Y Y Y Y
53466
0x3499 First Analog Offset
-32768
32767
1
F20
0
1
Y Y Y Y
53467
0x349A Second Analog Entry
0
36807
1
FC273
0
1
Y Y Y Y
53468
0x349B Second Analog Factor
0
65535
1
F3
0
1
Y Y Y Y
53469
0x349C Second Analog Offset
-32768
32767
1
F20
0
1
Y Y Y Y
53470
0x349D Third Analog Entry
0
36807
1
FC273
0
1
Y Y Y Y
53471
0x349E Third Analog Factor
0
65535
1
F3
0
1
Y Y Y Y
53472
0x349F Third Analog Offset
-32768
32767
1
F20
0
1
Y Y Y Y
53473
0x34A0 Fourth Analog Entry
0
36807
1
FC273
0
1
Y Y Y Y
53474
0x34A1 Fourth Analog Factor
0
65535
1
F3
0
1
Y Y Y Y
53475
0x34A2 Fourth Analog Offset
-32768
32767
1
F20
0
1
Y Y Y Y
53476
0x34A3 Fifth Analog Entry
0
36807
1
FC273
0
1
Y Y Y Y
53477
0x34A4 Fifth Analog Factor
0
65535
1
F3
0
1
Y Y Y Y
53478
0x34A5 Fifth Analog Offset
-32768
32767
1
F20
0
1
Y Y Y Y
53479
0x34A6 Sixth Analog Entry
0
36807
1
FC273
0
1
Y Y Y Y
53480
0x34A7 Sixth Analog Factor
0
65535
1
F3
0
1
Y Y Y Y
53481
0x34A8 Sixth Analog Offset
-32768
32767
1
F20
0
1
Y Y Y Y
53482
0x34A9 Seventh Analog Entry
0
36807
1
FC273
0
1
Y Y Y Y
53483
0x34AA Seventh Analog Factor
0
65535
1
F3
0
1
Y Y Y Y
53484
0x34AB Seventh Analog Offset
-32768
32767
1
F20
0
1
Y Y Y Y
53485
0x34AC Eighth Analog Entry
0
36807
1
FC273
0
1
Y Y Y Y
53486
0x34AD Eighth Analog Factor
0
65535
1
F3
0
1
Y Y Y Y
53487
0x34AE Eighth Analog Offset
-32768
32767
1
F20
0
1
Y Y Y Y
53488
0x34AF Ninth Analog Entry
0
36807
1
FC273
0
1
Y Y Y Y
53489
0x34B0 Ninth Analog Factor
0
65535
1
F3
0
1
Y Y Y Y
53490
0x34B1 Ninth Analog Offset
-32768
32767
1
F20
0
1
Y Y Y Y
Second ASDU
53501
0x34BC Second ASDU Ident Type 0
1
1
FC212
0
1
Y Y Y Y
53502
0x34BD Second ASDU Func Type 0
255
1
F0
0
1
Y Y Y Y
53503
0x34BE Second ASDU Info Num
0
255
1
F0
0
1
Y Y Y Y
53504
0x34BF Second ASDU Scan
Timeout
0
1000
1
s
F0
0
1
Y Y Y Y
53505
0x34C0 First Analog Entry
0
36807
1
FC273
0
1
Y Y Y Y
53506
0x34C1 First Analog Factor
0
65535
1
F3
0
1
Y Y Y Y
53507
0x34C2 First Analog Offset
-32768
32767
1
F20
0
1
Y Y Y Y
53508
0x34C3 Second Analog Entry
0
36807
1
FC273
0
1
Y Y Y Y
53509
0x34C4 Second Analog Factor
0
65535
1
F3
0
1
Y Y Y Y
Modbus
Address
Hex
Address
Description
Min
Max
Step Units
Format
Code
Factory
Default
Size in
Words
8
5
0
8
6
9
8
8
9
8
4
5
Содержание 850
Страница 26: ...3 6 8 SERIES PROTECTIVE RELAY PLATFORM COMMUNICATIONS GUIDE REAL TIME CLOCK CHAPTER 3 TIME PROTOCOLS...
Страница 40: ...4 14 8 SERIES PROTECTIVE RELAY PLATFORM COMMUNICATIONS GUIDE DNP IMPLEMENTATION CHAPTER 4 DNP PROTOCOL...
Страница 54: ...6 10 8 SERIES PROTECTIVE RELAY PLATFORM COMMUNICATIONS GUIDE INTEROPERABILITY CHAPTER 6 IEC 60870 5 104...
Страница 86: ...8 24 8 SERIES PROTECTIVE RELAY PLATFORM COMMUNICATIONS GUIDE THE IEC 61850 CONFIGURATOR CHAPTER 8 IEC 61850...
Страница 788: ...14 294 8 SERIES PROTECTIVE RELAY PLATFORM COMMUNICATIONS GUIDE CHAPTER 14 FORMAT CODES...
Страница 868: ...B 74 8 SERIES PROTECTIVE RELAY PLATFORM COMMUNICATIONS GUIDE PIXIT CHAPTER B IEC 61850 IMPLEMENTATION DETAILS...