8-4
8 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE
STATUS
CHAPTER 8: IEC 61850
CLIENT 1(8) IP ADDRESS
Range: 0, 0XFFFFFFFF
Default: 0
GOOSE Status
GGIO1 INDICATIONS
Path:
Status > Communications > GGIO1 Indications
The present state of the 32 GGIO1 Indications are shown here. There are up to 32 GGIO
indications that can be used to map any FlexLogic operand into the IED 61850 information
model. Default value is Off.
GOOSE STATUS
Path
:
Status > Communications > GOOSE Status
GOOSE 1 to 64 Status
Range: OFF, ON
Default: OFF
GOOSE HEADER
Path
:
Status > Communications > GOOSE HDR Status
GOOSE 1 to 64 H.Status
Range: OFF, ON
Default: OFF
GOOSE ANALOG
Path
:
Status > Communications > GOOSE Analog AV
FLOAT 1 to 24
Range:
Default: 0.0
SINT32 1 to 8
Range:
Default: 0
IEC 61850 STATUS
Path
:
Status > Communications > IEC 61850 Status
COMMS NOT VALIDATED OK
Range: NO, YES
Default: NO
COMMS NOT VALIDATED DONE
Range: YES, NO
Default: YES
COMMS VALIDATED OK
Range: YES, NO
Default: YES
COMMS VALIDATED DONE
Range: YES, NO
Default: YES
Содержание 850
Страница 26: ...3 6 8 SERIES PROTECTIVE RELAY PLATFORM COMMUNICATIONS GUIDE REAL TIME CLOCK CHAPTER 3 TIME PROTOCOLS...
Страница 40: ...4 14 8 SERIES PROTECTIVE RELAY PLATFORM COMMUNICATIONS GUIDE DNP IMPLEMENTATION CHAPTER 4 DNP PROTOCOL...
Страница 54: ...6 10 8 SERIES PROTECTIVE RELAY PLATFORM COMMUNICATIONS GUIDE INTEROPERABILITY CHAPTER 6 IEC 60870 5 104...
Страница 86: ...8 24 8 SERIES PROTECTIVE RELAY PLATFORM COMMUNICATIONS GUIDE THE IEC 61850 CONFIGURATOR CHAPTER 8 IEC 61850...
Страница 788: ...14 294 8 SERIES PROTECTIVE RELAY PLATFORM COMMUNICATIONS GUIDE CHAPTER 14 FORMAT CODES...
Страница 868: ...B 74 8 SERIES PROTECTIVE RELAY PLATFORM COMMUNICATIONS GUIDE PIXIT CHAPTER B IEC 61850 IMPLEMENTATION DETAILS...