CHAPTER 8: IEC 61850
THE IEC 61850 CONFIGURATOR
8 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE
8-17
Figure 8-9: Delete a Dataset Item
•
Select the row in which the dataset item is to be deleted then right click and select the
displayed “Delete FCDA” option.
Figure 8-10: Delete FCDA Option
Number of DAs Counter
Depending on the configured dataset items, the “Number of DAs” counter increases
automatically.
Figure 8-11: Dataset Properties
Maximum Report Control Blocks
The 8 Series relay supports a maximum of 4 report control blocks. Buffered and unbuffered
reports are both included in the maximum. The user can configure reports based on the
Report Configurations Supported table as follows.
Table 8-2: Report Configurations Supported
Buffered Report
Unbuffered Report
Total Reports
4
0
4
3
1
4
2
2
4
1
3
4