CHAPTER 8: IEC 61850
THE IEC 61850 CONFIGURATOR
8 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE
8-19
•
Dataset sources: Each GOOSE control block can be appended with dataset items in
this screen using a drag and drop operation.
–
DataSet Name
: The first character in the value of this attribute must be a letter
(upper or lower case). The rest of the characters must be a number, a letter (upper
or lower case) or a “_”. The maximum number of characters allowed is 32.
–
Description:
The maximum number of characters allowed is 32.
Figure 8-13: Goose TX Control Blocks and DataSet Sources Screen
The following buttons are available in the Goose Transmission window:
•
“Add GOOSE Control Block” button and “Remove GOOSE Control Block” button: Both
buttons are in the lower side of the screen.
•
Note that a GOOSE Control block can also be added by right clicking on “845” (or your
relay model number) which is under the GEDevice “tree”.
The “Remove Goose Control Block” button deletes a configured existing Goose control
block.
Содержание 850
Страница 26: ...3 6 8 SERIES PROTECTIVE RELAY PLATFORM COMMUNICATIONS GUIDE REAL TIME CLOCK CHAPTER 3 TIME PROTOCOLS...
Страница 40: ...4 14 8 SERIES PROTECTIVE RELAY PLATFORM COMMUNICATIONS GUIDE DNP IMPLEMENTATION CHAPTER 4 DNP PROTOCOL...
Страница 54: ...6 10 8 SERIES PROTECTIVE RELAY PLATFORM COMMUNICATIONS GUIDE INTEROPERABILITY CHAPTER 6 IEC 60870 5 104...
Страница 86: ...8 24 8 SERIES PROTECTIVE RELAY PLATFORM COMMUNICATIONS GUIDE THE IEC 61850 CONFIGURATOR CHAPTER 8 IEC 61850...
Страница 788: ...14 294 8 SERIES PROTECTIVE RELAY PLATFORM COMMUNICATIONS GUIDE CHAPTER 14 FORMAT CODES...
Страница 868: ...B 74 8 SERIES PROTECTIVE RELAY PLATFORM COMMUNICATIONS GUIDE PIXIT CHAPTER B IEC 61850 IMPLEMENTATION DETAILS...