GGIO3 Logical Node
Range: Enum
These are the control models supported: (0) status only, (1) direct-with-normal-
security. They can be configured under the Value column.
XCBR Logical Node
Range: the sboTimeout setting range is 500 to 60000 msec
The XCBR1 Pos sboTimeout setting is used to select SBO timeout value. To be
successful, the IEC 61850 "operate" command must be executed after the "select"
command within the XCBR1 Pos sboTimeout setting value.
XCBR-POS can be configured for status only, Direct operate, Select before operate,
Direct operate with enhanced, SBO enhanced.
3.
GGIO 1 Indications tab
(FlexLogic Operand Interface)
GGIO1 is a workaround that allows any 8 Series relay FlexLogic™ operands to be
mapped into the IED 61850 information model. Once in the model, the operand status
is visible via MMS services and may be added to datasets for GOOSE and reports.
There are up to 32 GGIO1 indications that can be used to map those digital values.
850.MMXU1$CF$A$phsA$db
850.MMXU1$CF$A$phsA$dbAng
850.MMXU1$CF$A$phsB$db
850.MMXU1$CF$A$phsB$dbAng
850.MMXU1$CF$A$phsC$db
850.MMXU1$CF$A$phsC$dbAng
850.MMXU1$CF$A$neut$db
850.MMXU1$CF$A$neut$dbAng
850.MMXU1$CF$A$net$db
850.MMXU1$CF$A$net$dbAng
850.MMXU1$CF$AuxV$db
850.MMXU1$CF$AuxV$dbAng
Supported Parameters (names begin with 845, 850, 869, or 889 depending on the specific relay)
Содержание 850
Страница 26: ...3 6 8 SERIES PROTECTIVE RELAY PLATFORM COMMUNICATIONS GUIDE REAL TIME CLOCK CHAPTER 3 TIME PROTOCOLS...
Страница 40: ...4 14 8 SERIES PROTECTIVE RELAY PLATFORM COMMUNICATIONS GUIDE DNP IMPLEMENTATION CHAPTER 4 DNP PROTOCOL...
Страница 54: ...6 10 8 SERIES PROTECTIVE RELAY PLATFORM COMMUNICATIONS GUIDE INTEROPERABILITY CHAPTER 6 IEC 60870 5 104...
Страница 86: ...8 24 8 SERIES PROTECTIVE RELAY PLATFORM COMMUNICATIONS GUIDE THE IEC 61850 CONFIGURATOR CHAPTER 8 IEC 61850...
Страница 788: ...14 294 8 SERIES PROTECTIVE RELAY PLATFORM COMMUNICATIONS GUIDE CHAPTER 14 FORMAT CODES...
Страница 868: ...B 74 8 SERIES PROTECTIVE RELAY PLATFORM COMMUNICATIONS GUIDE PIXIT CHAPTER B IEC 61850 IMPLEMENTATION DETAILS...