6-4
8 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE
INTEROPERABILITY
CHAPTER 6: IEC 60870-5-104
Table 6-2: Process information in control direction
Either the ASDUs of the set <45> to <51> or of the set <58> to <64> are used.
Table 6-3: System information in monitor direction
Table 6-4: System information in control direction
Table 6-5: Parameter in control direction
Table 6-6: File transfer
Number / description
Mnemonic
⊠
<45> := Single command
C_SC_NA_1
⊠
<46> := Double command
C_DC_NA_1
□
<47> := Regulating step command
C_RC_NA_1
□
<48> := Set point command, normalized value
C_SE_NA_1
□
<49> := Set point command, scaled value
C_SE_NB_1
□
<50> := Set point command, short floating point value
C_SE_NC_1
□
<51> := Bitstring of 32 bits
C_BO_NA_1
⊠
<58> := Single command with time tag CP56Time2a
C_SC_TA_1
⊠
<59> := Double command with time tag CP56Time2a
C_DC_TA_1
□
<60> := Regulating step command with time tag CP56Time2a
C_RC_TA_1
□
<61> := Set point command, normalized value with time tag CP56Time2a
C_SE_TA_1
□
<62> := Set point command, scaled value with time tag CP56Time2a
C_SE_TB_1
□
<63> := Set point command, short floating point value with time tag
CP56Time2a
C_SE_TC_1
□
<64> := Bitstring of 32 bits with time tag CP56Time2a
C_BO_TA_1
Number / description
Mnemonic
⊠
<70> := End of initialization
M_EI_NA_1
Number / description
Mnemonic
⊠
<100> := Interrogation command
C_IC_NA_1
⊠
<101> := Counter interrogation command
C_CI_NA_1
⊠
<102> := Read command
C_RD_NA_1
⊠
<103> := Clock synchronization command (see Clause 7.6 in standard)
C_CS_NA_1
⊠
<105> := Reset process command
C_RP_NA_1
⊠
<107> := Test command with time tag CP56Time2a
C_TS_TA_1
Number / description
Mnemonic
□
<110> := Parameter of measured value, normalized value
PE_ME_NA_1
⊠
<111> := Parameter of measured value, scaled value
PE_ME_NB_1
□
<112> := Parameter of measured value, short floating point value
PE_ME_NC_1
□
<113> := Parameter activation
PE_AC_NA_1
Number / description
Mnemonic
□
<120> := File ready
F_FR_NA_1
□
<121> := Section ready
F_SR_NA_1
□
<122> := Call directory, select file, call file, call section
F_SC_NA_1
□
<123> := Last section, last segment
F_LS_NA_1
□
<124> := Ack file, ack section
F_AF_NA_1
□
<125> := Segment
F_SG_NA_1
□
<126> := Directory (blank or X, available only in monitor [standard] direction) F_DR_TA_1
□
<127> := Query log - Request archive file
F_SC_NB_1
Содержание 850
Страница 26: ...3 6 8 SERIES PROTECTIVE RELAY PLATFORM COMMUNICATIONS GUIDE REAL TIME CLOCK CHAPTER 3 TIME PROTOCOLS...
Страница 40: ...4 14 8 SERIES PROTECTIVE RELAY PLATFORM COMMUNICATIONS GUIDE DNP IMPLEMENTATION CHAPTER 4 DNP PROTOCOL...
Страница 54: ...6 10 8 SERIES PROTECTIVE RELAY PLATFORM COMMUNICATIONS GUIDE INTEROPERABILITY CHAPTER 6 IEC 60870 5 104...
Страница 86: ...8 24 8 SERIES PROTECTIVE RELAY PLATFORM COMMUNICATIONS GUIDE THE IEC 61850 CONFIGURATOR CHAPTER 8 IEC 61850...
Страница 788: ...14 294 8 SERIES PROTECTIVE RELAY PLATFORM COMMUNICATIONS GUIDE CHAPTER 14 FORMAT CODES...
Страница 868: ...B 74 8 SERIES PROTECTIVE RELAY PLATFORM COMMUNICATIONS GUIDE PIXIT CHAPTER B IEC 61850 IMPLEMENTATION DETAILS...