4-12
8 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE
DNP IMPLEMENTATION
CHAPTER 4: DNP PROTOCOL
30
0
Analog Input
(Variation 0 is used
to request default
variation)
1 (read)
22 (assign class)
00, 01 (start-stop)
06 (no range, or all)
07, 08 (limited quantity)
17, 28 (index)
---
---
1
32-Bit Analog Input 1 (read)
22 (assign class)
00, 01 (start-stop)
06 (no range, or all)
07, 08 (limited quantity)
17, 28 (index)
129 (response)
00, 01 (start-stop)
17, 28 (index) (see
Note 2)
2
16-Bit Analog Input 1 (read)
22 (assign class)
00, 01 (start-stop)
06 (no range, or all)
07, 08 (limited quantity)
17, 28 (index)
129 (response)
00, 01 (start-stop)
17, 28 (index) (see
Note 2)
3
32-Bit Analog Input
without Flag
1 (read)
22 (assign class)
00, 01 (start-stop)
06 (no range, or all)
07, 08 (limited quantity)
17, 28 (index)
129 (response)
00, 01 (start-stop)
17, 28 (index) (see
Note 2)
4
16-Bit Analog Input
without Flag
1 (read)
22 (assign class)
00, 01 (start-stop)
06 (no range, or all)
07, 08 (limited quantity)
17, 28 (index)
129 (response)
00, 01 (start-stop)
17, 28 (index) (see
Note 2)
5
short floating point
1 (read)
22 (assign class)
00, 01 (start-stop)
06 (no range, or all)
07, 08 (limited quantity)
17, 28 (index)
129 (response)
00, 01 (start-stop)
17, 28 (index) (see
Note 2)
32
0
Analog Change
Event (Variation 0 is
used to request
default variation)
1 (read)
06 (no range, or all)
07, 08 (limited quantity)
---
---
1
32-Bit Analog
Change Event
without Time
1 (read)
06 (no range, or all)
07, 08 (limited quantity)
129 (response)
130 (unsol. resp.)
17, 28 (index)
2
16-Bit Analog
Change Event
without Time
1 (read)
06 (no range, or all)
07, 08 (limited quantity)
129 (response)
130 (unsol. resp.)
17, 28 (index)
3
32-Bit Analog
Change Event with
Time
1 (read)
06 (no range, or all)
07, 08 (limited quantity)
129 (response)
130 (unsol. resp.)
17, 28 (index)
4
16-Bit Analog
Change Event with
Time
1 (read)
06 (no range, or all)
07, 08 (limited quantity)
129 (response)
130 (unsol. resp.)
17, 28 (index)
5
short floating point
Analog Change
Event without Time
1 (read)
06 (no range, or all)
07, 08 (limited quantity)
129 (response)
130 (unsol. resp.)
17, 28 (index)
7
short floating point
Analog Change
Event with Time
1 (read)
06 (no range, or all)
07, 08 (limited quantity)
129 (response)
130 (unsol. resp.)
17, 28 (index)
34
0
Analog Input
Reporting Deadband
(Variation 0 is used
to request default
variation)
1 (read)
00, 01 (start-stop)
06 (no range, or all)
07, 08 (limited quantity)
17, 28 (index)
---
---
1
16-bit Analog Input
Reporting Deadband
(default - see Note 1)
1 (read)
00, 01 (start-stop)
06 (no range, or all)
07, 08 (limited quantity)
17, 28 (index)
129 (response)
00, 01 (start-stop)
17, 28 (index) (see
Note 2)
2 (write)
00, 01 (start-stop)
07, 08 (limited quantity)
17, 28 (index)
---
---
2
32-bit Analog Input
Reporting Deadband
1 (read)
00, 01 (start-stop)
06 (no range, or all)
07, 08 (limited quantity)
17, 28 (index)
129 (response)
00, 01 (start-stop)
17, 28 (index) (see
Note 2)
OBJECT
REQUEST
RESPONSE
OBJECT
NO.
VARIATION
NO.
DESCRIPTION
FUNCTION
CODES (DEC)
QUALIFIER CODES (HEX) FUNCTION CODES
(DEC)
QUALIFIER CODES
(HEX)
Содержание 850
Страница 26: ...3 6 8 SERIES PROTECTIVE RELAY PLATFORM COMMUNICATIONS GUIDE REAL TIME CLOCK CHAPTER 3 TIME PROTOCOLS...
Страница 40: ...4 14 8 SERIES PROTECTIVE RELAY PLATFORM COMMUNICATIONS GUIDE DNP IMPLEMENTATION CHAPTER 4 DNP PROTOCOL...
Страница 54: ...6 10 8 SERIES PROTECTIVE RELAY PLATFORM COMMUNICATIONS GUIDE INTEROPERABILITY CHAPTER 6 IEC 60870 5 104...
Страница 86: ...8 24 8 SERIES PROTECTIVE RELAY PLATFORM COMMUNICATIONS GUIDE THE IEC 61850 CONFIGURATOR CHAPTER 8 IEC 61850...
Страница 788: ...14 294 8 SERIES PROTECTIVE RELAY PLATFORM COMMUNICATIONS GUIDE CHAPTER 14 FORMAT CODES...
Страница 868: ...B 74 8 SERIES PROTECTIVE RELAY PLATFORM COMMUNICATIONS GUIDE PIXIT CHAPTER B IEC 61850 IMPLEMENTATION DETAILS...