8 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE
THE IEC 61850 CONFIGURATOR
CHAPTER 8: IEC 61850
All the available parameters of the Report control block are displayed when clicking
“Report Advanced Configuration”. Respective OptFields, TrgOps can be configured by
either selecting “True” or “False”. Buffer time is given in milliseconds.
Figure 8-6: Advanced Configuration
Configure Dataset Items
1.
Select the required logical node under GEDevice > 8 Series relay tree.
2.
Go to the required dataset item.
3.
Drag and drop the item to the “DataSet Elements” section, see the following DataSet
Sources/DataSet figure.
Figure 8-7: DataSet Sources Window
Change the Order of Configured Dataset Items
1.
Select the row in which the order is to be changed.
2.
Use the “up” arrow if you want to shift the row to the top. Use the “down” arrow to
shift the row down.
Figure 8-8: Re-order DataSet Items
Delete a Dataset Item
The following list gives the two methods that can be used to delete a dataset item.
•
Select the row in which the dataset item is to be deleted and click the “x” button.
Содержание 850
Страница 26: ...3 6 8 SERIES PROTECTIVE RELAY PLATFORM COMMUNICATIONS GUIDE REAL TIME CLOCK CHAPTER 3 TIME PROTOCOLS...
Страница 40: ...4 14 8 SERIES PROTECTIVE RELAY PLATFORM COMMUNICATIONS GUIDE DNP IMPLEMENTATION CHAPTER 4 DNP PROTOCOL...
Страница 54: ...6 10 8 SERIES PROTECTIVE RELAY PLATFORM COMMUNICATIONS GUIDE INTEROPERABILITY CHAPTER 6 IEC 60870 5 104...
Страница 86: ...8 24 8 SERIES PROTECTIVE RELAY PLATFORM COMMUNICATIONS GUIDE THE IEC 61850 CONFIGURATOR CHAPTER 8 IEC 61850...
Страница 788: ...14 294 8 SERIES PROTECTIVE RELAY PLATFORM COMMUNICATIONS GUIDE CHAPTER 14 FORMAT CODES...
Страница 868: ...B 74 8 SERIES PROTECTIVE RELAY PLATFORM COMMUNICATIONS GUIDE PIXIT CHAPTER B IEC 61850 IMPLEMENTATION DETAILS...