CHAPTER B: IEC 61850 IMPLEMENTATION DETAILS
PIXIT
8 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE
B-69
PIXIT for GOOSE publish model
ID
Ed
Description
Value / Clarification
Gp1
1,2
Can the test (Ed1) / simulation (Ed2) flag in the
published GOOSE be set
N
Gp2
1
What is the Behavior when the GOOSE publish
configuration is incorrect
DUT keeps GoEna=F
Configuration tool does not allow wrong configuration to be
uploaded into device. e.g.: empty dataset.
Gp3
1,2
Published FCD supported common data classes
are
SPS, INS, ENS, ACT, ACD, MV, CMV, SAV, WYE, DEL, SEQ, INC, ENC, SPC,
DPC, INC, ENC. (Only the elements with FC=ST or MX will be
published).
Gp4
1,2
What is the slow retransmission time
Is it fixed or configurable
Configured by SCL on GoCB MaxTime
Gp5
1,2
What is the fastest retransmission time
Is it fixed or configurable
Fixed. MinTime = 5 ms
Gp6
-
Can the GOOSE publish be turned on / off by using
SetGoCBValues(GoEna)
Y
Gp7
1,2
What is the initial GOOSE sqNum after restart
sqNum = 1
Gp8
1
May the GOOSE data set contain:
- structured data objects (FCD)
- timestamp data attributes
Y
Y (timestamp attributes are not supported)
Gp9
2
How is the retransmission curve after a change.
- sqNum = 0 New change
- sqNum = 1 -> 5ms later with TAL = 1000
- sqNum = 2 -> 10ms later with TAL = 1000
- sqNum = 3 -> 15ms later with TAL = 4000
- sqNum = 4 -> 1000ms later with TAL = Update time* x 4
- sqNum = 5 -> Update time* later with TAL = Update time* x 4
- sqNum = 6-> Update time* later with TAL = Update time* x 4
- sqNum = 7 ……..
- ………….
*
Update time
is configured in the Enervista 8 Series Setup
Содержание 850
Страница 26: ...3 6 8 SERIES PROTECTIVE RELAY PLATFORM COMMUNICATIONS GUIDE REAL TIME CLOCK CHAPTER 3 TIME PROTOCOLS...
Страница 40: ...4 14 8 SERIES PROTECTIVE RELAY PLATFORM COMMUNICATIONS GUIDE DNP IMPLEMENTATION CHAPTER 4 DNP PROTOCOL...
Страница 54: ...6 10 8 SERIES PROTECTIVE RELAY PLATFORM COMMUNICATIONS GUIDE INTEROPERABILITY CHAPTER 6 IEC 60870 5 104...
Страница 86: ...8 24 8 SERIES PROTECTIVE RELAY PLATFORM COMMUNICATIONS GUIDE THE IEC 61850 CONFIGURATOR CHAPTER 8 IEC 61850...
Страница 788: ...14 294 8 SERIES PROTECTIVE RELAY PLATFORM COMMUNICATIONS GUIDE CHAPTER 14 FORMAT CODES...
Страница 868: ...B 74 8 SERIES PROTECTIVE RELAY PLATFORM COMMUNICATIONS GUIDE PIXIT CHAPTER B IEC 61850 IMPLEMENTATION DETAILS...