4. Service parts information
4-1. Compressor
Diagnosis method of compressor (If outdoor unit LED displays error, refer to troubleshooting)
Does not start up
Stops soon after starting up
Abnormal noise
↓
↓
↓
Is there open or loose con-
nection cable?
Is there open or loose con-
nection cable?
Check if vibration noise by
loose bolt or contact noise of
piping is happening.
↓
↓
↓
Check main PCB, connection
of compressor, and winding
resistance.
(Refer to the next page)
→ If there is no failure, the
defect of compressor is con-
sidered (Locked compressor
due to clogged dirt or less oil)
Is gas pipe valve open?
(Low pressure is too low)
Defective compressor can be
considered.
(due to inside dirt clogging or
broken component)
↓
↓
↓
Replace compressor.
Check if refrigerant is
leaking.
MPa
MPa
Replace compressor.
↓
↓
↓
End
Check if strainer is clogged.
(Refer to outdoor EEV in this
chapter.)
End
↓
Check main PCB, connection of compressor and winding resis-
tance. (Refer to the next page)
→ If there is no failure, the defect of compressor can be consid-
ered. (Compression part broken or valve defective.)
↓
Replace compressor.
↓
End
4-1. Compressor
- (03-49) -
4. Service parts information
TROUBLESHOOTING
TROUBLESHOOTING
Содержание ABHG54KRTA
Страница 4: ......
Страница 5: ...1 GENERAL INFORMATION 2020 04 16 SR_CH01_AB007EG_01 ...
Страница 12: ...2 2 Outdoor unit 01 6 2 Dimensions GENERAL INFORMATION GENERAL INFORMATION ...
Страница 13: ...2 TECHNICAL DATA AND PARTS LIST 2020 11 16 SR_CH02_AB007EG_02 ...
Страница 31: ...3 TROUBLESHOOTING 2020 07 29 SR_CH03_AB007EG_01 ...
Страница 34: ......
Страница 95: ...4 CONTROL AND FUNCTIONS 2020 07 29 SR_CH04_AB007EG_01 ...
Страница 97: ...8 8 High temperature and high pressure release control 04 29 CONTENTS continued ...
Страница 98: ......
Страница 129: ...5 FILED WORKING 2020 07 29 SR_CH05_AB007EG_01 ...