7. Various control
7-1. Auto restart
When the power was interrupted by a power failure etc. during operation, the operation contents at
that time are memorized and when the power is recovered, operation is automatically started with
the memorized operation contents.
Operation contents memorized when the power is interrupted
Operation mode
Setting temperature
Fan mode setting
Timer mode and set time (set by wireless remote controller)
Airflow direction setting
Swing
ECONOMY operation
10 °C HEAT operation
Outdoor low noise operation
7-2. 10 °C HEAT operation
10 °C HEAT operation performs as below setting when pressing 10 °C HEAT button.
Operation mode
Heating
Setting temperature
10°C
Fan mode
AUTO
LED display
Economy
Defrost operation
Operate as normal
7-3. ECONOMY operation
The ECONOMY operation starts by pressing ECONOMY button on the remote controller.
The ECONOMY operation is almost the same operation as below settings.
Mode
Cooling/Dry
Heating
Target temperature
Setting tempe1°C
Setting temperature -1°C
7-4. POWERFUL operation
The POWERFUL operation starts by pressing POWERFUL button on the remote controller.
The indoor unit and outdoor unit operate at maximum power as shown in the table below.
Compressor frequency
Maximum
Fan mode
POWERFUL
Vertical airflow direction
louver setting
Cooling
3
Dry
Heating
5
Release condition:
• Cooling/Dry
Room temperature ≤ Setting temperature -0.5°C or Operation time has passed 20 minutes.
• Heating
Room temperature ≥ Setting tempe0.5°C or Operation time has passed 20 minutes.
7-1. Auto restart
- (04-20) -
7. Various control
CONTROL AND
FUNCTIONS
CONTROL AND
FUNCTIONS
Содержание ABHG54KRTA
Страница 4: ......
Страница 5: ...1 GENERAL INFORMATION 2020 04 16 SR_CH01_AB007EG_01 ...
Страница 12: ...2 2 Outdoor unit 01 6 2 Dimensions GENERAL INFORMATION GENERAL INFORMATION ...
Страница 13: ...2 TECHNICAL DATA AND PARTS LIST 2020 11 16 SR_CH02_AB007EG_02 ...
Страница 31: ...3 TROUBLESHOOTING 2020 07 29 SR_CH03_AB007EG_01 ...
Страница 34: ......
Страница 95: ...4 CONTROL AND FUNCTIONS 2020 07 29 SR_CH04_AB007EG_01 ...
Страница 97: ...8 8 High temperature and high pressure release control 04 29 CONTENTS continued ...
Страница 98: ......
Страница 129: ...5 FILED WORKING 2020 07 29 SR_CH05_AB007EG_01 ...