3. External input and output for indoor unit
Terminal
(Ext.in)
CN65
(Ext.in/out PCB)
CN47
(Ext.out)
Rotary switch
SW2
SW1
Fig. External input and output PCB
Fig. Indoor unit PCB
PCB
External input External output Connector
Input select
Input
signal
External
connect kit
(Optional
parts)
Indoor unit
Operation/Stop
Forced stop
—
Terminal
Dry contact
Edge
—
—
Operation status
CN47
—
—
UTY-XWZXZG
Error status
Indoor unit fan
operation status
External heater
output
External input
and output
(UTY-XCSX)
Operation/Stop
—
Input 1/
Input 2
Dry contact/
Apply voltage
Edge/
Pulse
—
Forced
thermostat off
Input 1
Edge
—
Operation status
Output 1
Output 2
Output 3
—
—
—
Error status
Indoor unit status
External heater
output
3-1. External input
• “Operation/Stop” mode or "Forced stop" mode can be selected with function setting of indoor unit.
• A twisted pair cable (22AWG) should be used. Maximum length of cable is 150 m.
• The wire connection should be separate from the power cable line.
¢
Indoor unit
Indoor unit functions such as Operation/Stop can be done by using indoor unit terminals.
1
2
Terminal
*1: The switch can be used on the following condition: DC 12 V to 24 V, 1 mA to 15 mA.
3-1. External input
- (05-10) -
3. External input and output for indoor unit
FIELD
WORKING
FIELD
WORKING
Содержание ABHG54KRTA
Страница 4: ......
Страница 5: ...1 GENERAL INFORMATION 2020 04 16 SR_CH01_AB007EG_01 ...
Страница 12: ...2 2 Outdoor unit 01 6 2 Dimensions GENERAL INFORMATION GENERAL INFORMATION ...
Страница 13: ...2 TECHNICAL DATA AND PARTS LIST 2020 11 16 SR_CH02_AB007EG_02 ...
Страница 31: ...3 TROUBLESHOOTING 2020 07 29 SR_CH03_AB007EG_01 ...
Страница 34: ......
Страница 95: ...4 CONTROL AND FUNCTIONS 2020 07 29 SR_CH04_AB007EG_01 ...
Страница 97: ...8 8 High temperature and high pressure release control 04 29 CONTENTS continued ...
Страница 98: ......
Страница 129: ...5 FILED WORKING 2020 07 29 SR_CH05_AB007EG_01 ...