2-31. E: A1. Discharge temperature error (Outdoor unit)
Indicator
Wired remote
controller
Error code
E: A1
Detective actuator
Outdoor unit main PCB
Protection stop by discharge temperature ≥ 110 °C
during compressor operation generated 2 times within
24 hours.
Discharge temperature thermistor
Forecast of cause
3-way valve not opened
EEV defective, strainer clogged
Outdoor unit operation failure, foreign matter on heat
exchanger
Discharge temperature thermistor failure
Insufficient refrigerant
Main PCB failure
Check point 1. Check if 3-way valve is open
If the 3-way valve is closed, open the 3-way valve and check operation.
NOTE:
For cooling operation, check gas side of the 3-way valve.
For heating operation, check liquid side of the 3-way valve.
↓
Check point 2. Check the electronic expansion valve (EEV) and strainer
•
Check if EEV open.
Refer to outdoor unit Electronic Expansion Valve (EEV) in
•
Check the strainer clogging.
↓
Check point 3. Check the outdoor unit fan and heat exchanger
•
Check for foreign object at heat exchanger
•
Check if fan can be rotated by hand.
•
Check the motor. (Refer to outdoor unit fan motor in
↓
Check point 4. Check the discharge thermistor
The discharge temperature thermistor characteristics check. (Check by disconnecting thermistor
from PCB.)
NOTE:
For the characteristics of the thermistor, refer to
"Thermistor resistance values"
↓
2-31. E: A1. Discharge temperature error (Outdoor unit)
- (03-37) -
2. Troubleshooting with error code
TROUBLESHOOTING
TROUBLESHOOTING
Содержание ABHG54KRTA
Страница 4: ......
Страница 5: ...1 GENERAL INFORMATION 2020 04 16 SR_CH01_AB007EG_01 ...
Страница 12: ...2 2 Outdoor unit 01 6 2 Dimensions GENERAL INFORMATION GENERAL INFORMATION ...
Страница 13: ...2 TECHNICAL DATA AND PARTS LIST 2020 11 16 SR_CH02_AB007EG_02 ...
Страница 31: ...3 TROUBLESHOOTING 2020 07 29 SR_CH03_AB007EG_01 ...
Страница 34: ......
Страница 95: ...4 CONTROL AND FUNCTIONS 2020 07 29 SR_CH04_AB007EG_01 ...
Страница 97: ...8 8 High temperature and high pressure release control 04 29 CONTENTS continued ...
Страница 98: ......
Страница 129: ...5 FILED WORKING 2020 07 29 SR_CH05_AB007EG_01 ...