3-3. No operation (Power is on)
Forecast of cause
Setting/ Connection failure
External cause
Electrical components defective
Check point 1. Check indoor and outdoor installation condition
•
Indoor unit:
–
Check incorrect wiring between indoor unit and remote controller.
–
Check if there is an open cable connection.
•
Are these indoor unit, outdoor unit, and remote controller suitable model numbers to connect?
-> If there is some abnormal condition, correct it by referring to the installation manual and “DESIGN
& TECHNICAL MANUAL”.
↓
Turn off the power and check correct followings.
•
Is there loose or removed communication line of indoor unit and outdoor unit?
↓
Check point 2. Check external cause at indoor and outdoor (Voltage drop or Noise)
•
Instant drop: Check if there is a large load electric apparatus in the same circuit.
•
Momentary power failure: Check if there is a defective contact or leak current in the power sup-
ply circuit.
•
Noise: Check if there is any equipment causing harmonic wave near electric line. (Neon bulb or
electric equipment that may cause harmonic wave)
Check the complete insulation of grounding.
↓
Check point 3. Check wired remote controller and controller PCB
Check voltage at CN14 (terminal 1—3, terminal 1—2) of main PCB.
(Power supply to remote controller)
•
If it is DC 12 V, remote controller is failure. (The controller PCB is normal)
-> Replace remote controller.
•
If it is DC 0 V, controller PCB is failure. (Check the remote controller once
again)
-> Replace controller PCB.
↓
Check point 4. Replace main PCB
If check point 1 to 3 do not improve the symptom, change main PCB.
↓
End
3-3. No operation (Power is on)
- (03-44) -
3. Troubleshooting without error code
TROUBLESHOOTING
TROUBLESHOOTING
Содержание ABHG54KRTA
Страница 4: ......
Страница 5: ...1 GENERAL INFORMATION 2020 04 16 SR_CH01_AB007EG_01 ...
Страница 12: ...2 2 Outdoor unit 01 6 2 Dimensions GENERAL INFORMATION GENERAL INFORMATION ...
Страница 13: ...2 TECHNICAL DATA AND PARTS LIST 2020 11 16 SR_CH02_AB007EG_02 ...
Страница 31: ...3 TROUBLESHOOTING 2020 07 29 SR_CH03_AB007EG_01 ...
Страница 34: ......
Страница 95: ...4 CONTROL AND FUNCTIONS 2020 07 29 SR_CH04_AB007EG_01 ...
Страница 97: ...8 8 High temperature and high pressure release control 04 29 CONTENTS continued ...
Страница 98: ......
Страница 129: ...5 FILED WORKING 2020 07 29 SR_CH05_AB007EG_01 ...