Error status
Function
setting /
Rotary SW of External
input and output PCB
External output
Output signal
Command
60-09 / B
Output of indoor unit
CN47
Low → High
Error
High → Low
Normal
60-00 / 2
External input and output
PCB
Output 1
Off → On
Error
On → Off
Normal
60-00 / 1
Output 2
Off → On
Error
60-10 / C
On → Off
Normal
60-11 / D
Output 3
Off → On
Error
On → Off
Normal
The output is ON when an error is generated for the indoor unit.
Error
Normal
High
Low
CN47
On
Off
Output 1, 2, 3
Indoor unit
¢
Indoor unit fan operation status
Function
setting /
Rotary SW of External
input and output PCB
External output
Output signal
Command
60-10 / C
Output of indoor unit
CN47
Low → High
Fan run
High → Low
Fan stop
60-00 / 2
60-09 / B
60-11 / D
External input and output
PCB
Output 2
Off → On
Fan run
On → Off
Fan stop
60-00 / 1
Output 3
Off → On
Fan run
On → Off
Fan stop
Output signal
Condition
On
The indoor unit fan is operating.
Low → High
Off
The fan is stopped or during cold air prevention.
High → Low
During thermostat off when in dry mode operation.
Fan run
Fan stop
High
Low
CN47
On
Off
Output 2, 3
Indoor unit
3-4. Details of function
- (05-19) -
3. External input and output for indoor unit
FIELD
WORKING
FIELD
WORKING
Содержание ABHG54KRTA
Страница 4: ......
Страница 5: ...1 GENERAL INFORMATION 2020 04 16 SR_CH01_AB007EG_01 ...
Страница 12: ...2 2 Outdoor unit 01 6 2 Dimensions GENERAL INFORMATION GENERAL INFORMATION ...
Страница 13: ...2 TECHNICAL DATA AND PARTS LIST 2020 11 16 SR_CH02_AB007EG_02 ...
Страница 31: ...3 TROUBLESHOOTING 2020 07 29 SR_CH03_AB007EG_01 ...
Страница 34: ......
Страница 95: ...4 CONTROL AND FUNCTIONS 2020 07 29 SR_CH04_AB007EG_01 ...
Страница 97: ...8 8 High temperature and high pressure release control 04 29 CONTENTS continued ...
Страница 98: ......
Страница 129: ...5 FILED WORKING 2020 07 29 SR_CH05_AB007EG_01 ...