Sleep timer
If the sleep timer is set, the room temperature is monitored and the operation is stopped auto-
matically. If the operation mode or the set temperature is change after the sleep timer is set, the
operation is continued according to the changed setting of the sleep timer from that time on.
• In the cooling operation mode
When the sleep timer is set, the setting temperature is increased 1°C. It increases the setting
temperature another 1°C after 1 hour. After that, the setting temperature is not changed and
the operation is stopped at the setting time.
Set temperature rises
Ts: Set temperature
Stop of operation
Ts
+2°C
Set
60 min
+1°C
• In the heating operation mode
When the sleep timer is set, the setting temperature is decreased 1°C. It decreases the setting
temperature another 1°C every 30 minutes. Upon lowering 4°C, the setting temperature is not
changed and the operation is stopped at the setting time.
Set
Ts
-2°C
-1°C
-3°C
-4°C
Ts: Set temperature
30 min
30 min
30 min
Stop of operation
Set temperature rises
5-1. Wireless remote control
- (04-14) -
5. Timer operation control
CONTROL AND
FUNCTIONS
CONTROL AND
FUNCTIONS
Содержание ABHG54KRTA
Страница 4: ......
Страница 5: ...1 GENERAL INFORMATION 2020 04 16 SR_CH01_AB007EG_01 ...
Страница 12: ...2 2 Outdoor unit 01 6 2 Dimensions GENERAL INFORMATION GENERAL INFORMATION ...
Страница 13: ...2 TECHNICAL DATA AND PARTS LIST 2020 11 16 SR_CH02_AB007EG_02 ...
Страница 31: ...3 TROUBLESHOOTING 2020 07 29 SR_CH03_AB007EG_01 ...
Страница 34: ......
Страница 95: ...4 CONTROL AND FUNCTIONS 2020 07 29 SR_CH04_AB007EG_01 ...
Страница 97: ...8 8 High temperature and high pressure release control 04 29 CONTENTS continued ...
Страница 98: ......
Страница 129: ...5 FILED WORKING 2020 07 29 SR_CH05_AB007EG_01 ...