5) Room temperature control for wired remote controller sensor
Depending on the installed environment, correction of the wire remote temperature sensor may be
required. Select the appropriate control setting according to the installed environment.
To change this setting, set Function 42 to Both “01”.
Ensure that the Thermo Sensor icon is displayed on the remote controller screen.
Function number
Setting value
Setting description
Factory
setting
35
(For cooling)
36
(For heating)
00
Standard setting
♦
01
No correction 0.0°C
02
-0.5 °C
More cooling
Less heating
03
-1.0 °C
04
-1.5 °C
05
-2.0 °C
06
-2.5 °C
07
-3.0 °C
08
-3.5 °C
09
-4.0 °C
10
+0.5 °C
Less cooling
More heating
11
+1.0 °C
12
+1.5 °C
13
+2.0 °C
14
+2.5 °C
15
+3.0 °C
16
+3.5 °C
17
+4.0 °C
6) Auto restart
Enables or disables automatic restart after a power interruption.
Function number
Setting value
Setting description
Factory setting
40
00
Enable
♦
01
Disable
NOTE:
Auto restart is an emergency function such as for power outage etc. Do not attempt to use
this function in normal operation. Be sure to operate the unit by remote controller or exter-
nal device.
7) Room temperature sensor switching
(Only for wired remote controller)
When using the wired remote controller temperature sensor, change the setting to "Both" (01).
Function number
Setting value
Setting description
Factory setting
42
00
Indoor unit
♦
01
Both
00: Sensor on the indoor unit is active.
01: Sensors on both indoor unit and wired remote controller are active.
NOTE:
Remote controller sensor must be turned on by using the remote controller.
1-1. Function settings by using remote controller
- (05-3) -
1. Function settings for indoor unit
FIELD
WORKING
FIELD
WORKING
Содержание ABHG54KRTA
Страница 4: ......
Страница 5: ...1 GENERAL INFORMATION 2020 04 16 SR_CH01_AB007EG_01 ...
Страница 12: ...2 2 Outdoor unit 01 6 2 Dimensions GENERAL INFORMATION GENERAL INFORMATION ...
Страница 13: ...2 TECHNICAL DATA AND PARTS LIST 2020 11 16 SR_CH02_AB007EG_02 ...
Страница 31: ...3 TROUBLESHOOTING 2020 07 29 SR_CH03_AB007EG_01 ...
Страница 34: ......
Страница 95: ...4 CONTROL AND FUNCTIONS 2020 07 29 SR_CH04_AB007EG_01 ...
Страница 97: ...8 8 High temperature and high pressure release control 04 29 CONTENTS continued ...
Страница 98: ......
Страница 129: ...5 FILED WORKING 2020 07 29 SR_CH05_AB007EG_01 ...