When function setting is "Forced stop" mode
• In the case of "Edge" input
Function
setting /
Rotary SW of
External input and
output PCB
External input
Input signal
Command
46-02
-
Input of indoor unit
Terminal
Off → On
Forced stop
On → Off
Normal
60-00 / 1
External input and
output PCB
Input 1
Off → On
Forced stop
On → Off
Normal
On
Off
Forced stop
Normal
Operation
Stop
Remote controller
On
On
Indoor unit
On
Input
• In the case of "Pulse" input
Function
setting /
Rotary SW of
External input and
output PCB
External input
Input signal
Command
46-02
60-00 / 1
External input and
output PCB
Input 1
Pulse
Forced stop
Input 2
Pulse
Normal
On
Off
Operation
Stop
Remote controller
On
Off
Forced stop
Normal
Input 1
Input 2
On
On
On
Indoor unit
NOTES:
• When the forced stop is triggered, indoor unit stops and Operation/Stop operation by the re-
mote controller is restricted.
• When forced stop function is used with forming a remote controller group, connect the same
equipment to each indoor unit within the group.
3-4. Details of function
- (05-16) -
3. External input and output for indoor unit
FIELD
WORKING
FIELD
WORKING
Содержание ABHG54KRTA
Страница 4: ......
Страница 5: ...1 GENERAL INFORMATION 2020 04 16 SR_CH01_AB007EG_01 ...
Страница 12: ...2 2 Outdoor unit 01 6 2 Dimensions GENERAL INFORMATION GENERAL INFORMATION ...
Страница 13: ...2 TECHNICAL DATA AND PARTS LIST 2020 11 16 SR_CH02_AB007EG_02 ...
Страница 31: ...3 TROUBLESHOOTING 2020 07 29 SR_CH03_AB007EG_01 ...
Страница 34: ......
Страница 95: ...4 CONTROL AND FUNCTIONS 2020 07 29 SR_CH04_AB007EG_01 ...
Страница 97: ...8 8 High temperature and high pressure release control 04 29 CONTENTS continued ...
Страница 98: ......
Страница 129: ...5 FILED WORKING 2020 07 29 SR_CH05_AB007EG_01 ...