3-2. External output
Use an external output cable with appropriate external dimension, depending on the number of ca-
bles to be installed.
¢
Indoor unit
• A twisted pair cable (22AWG) should be used. Maximum length of cable is 25 m.
• Output voltage: High DC 12 V ± 2 V, Low 0 V.
• Permissible current: 50 mA
• For details, refer to
Chapter 3-3. "Combination of external input and output"
When indicator, etc. are connected directly
Example:
Function setting 60 is set to "00"
1
2
CN47
LED
PCB
Resistor
Connected unit
+
-
When connecting with a device equipped with a power supply
Example:
Function setting 60 is set to "00"
1
2
Connected device
CN47
PCB
Connected unit
Relay
(Operation status)
-
+
¢
External input and output PCB
• A twisted pair cable (22AWG) should be used.
• Permissible voltage and current: DC 5 V to 30 V / 3 A, AC 30 V to 250 V / 3 A
• For details, refer to
Chapter 3-3. "Combination of external input and output"
1
2
3
4
5
6
Power supply
Power supply
Power supply
PCB
Connected device 1
(Operation status)
Connected device 2
(Error status)
(Indoor unit fan
operation status)
Connected device 3
Example
3-2. External output
- (05-12) -
3. External input and output for indoor unit
FIELD
WORKING
FIELD
WORKING
Содержание ABHG54KRTA
Страница 4: ......
Страница 5: ...1 GENERAL INFORMATION 2020 04 16 SR_CH01_AB007EG_01 ...
Страница 12: ...2 2 Outdoor unit 01 6 2 Dimensions GENERAL INFORMATION GENERAL INFORMATION ...
Страница 13: ...2 TECHNICAL DATA AND PARTS LIST 2020 11 16 SR_CH02_AB007EG_02 ...
Страница 31: ...3 TROUBLESHOOTING 2020 07 29 SR_CH03_AB007EG_01 ...
Страница 34: ......
Страница 95: ...4 CONTROL AND FUNCTIONS 2020 07 29 SR_CH04_AB007EG_01 ...
Страница 97: ...8 8 High temperature and high pressure release control 04 29 CONTENTS continued ...
Страница 98: ......
Страница 129: ...5 FILED WORKING 2020 07 29 SR_CH05_AB007EG_01 ...