1-4. Compressor frequency at normal start-up
¢
Model: AOHG54KRTA
Compressor frequency soon after starting is controlled as below.
Frequency I
Frequency II
Frequency III
Frequency IV
Frequency V
Frequency VI
Frequency VII
Time 1
Time 2
Time 3
Time 4
Time 5
Time 6
Time 7
Frequency VIII
Time 8
Frequency IX
Frequency X
Time 9
Time 10
• Normal operation
Frequency
(rps)
I
II
III
IV
V
VI
VII
VIII
IX
X
41
46
51
57
60
72
81
91
100
110
Time (sec)
1
2
3
4
5
6
7
8
9
10
60
120
180
240
360
420
480
540
600
660
• Special operation
Frequency
(rps)
I
II
III
IV
V
VI
VII
VIII
IX
X
41
46
51
57
60
72
81
91
100
110
Time (sec)
1
2
3
4
5
6
7
8
9
10
120
185
245
305
605
665
725
785
845
1,000
NOTES:
• Normal operation:
– Cooling and dry mode
• Below 3 hours from the compressor stop and the compressor thermistor ≥ 15 °C
• After defrost operation
– Other than when the compressor starts for the first time since the breaker turns on
• Special operation:
– Other than the normal operation condition
– When the compressor starts for the first time since the breaker turns on
1-4. Compressor frequency at normal start-up
- (04-3) -
1. Compressor frequency control
CONTROL AND
FUNCTIONS
CONTROL AND
FUNCTIONS
Содержание ABHG54KRTA
Страница 4: ......
Страница 5: ...1 GENERAL INFORMATION 2020 04 16 SR_CH01_AB007EG_01 ...
Страница 12: ...2 2 Outdoor unit 01 6 2 Dimensions GENERAL INFORMATION GENERAL INFORMATION ...
Страница 13: ...2 TECHNICAL DATA AND PARTS LIST 2020 11 16 SR_CH02_AB007EG_02 ...
Страница 31: ...3 TROUBLESHOOTING 2020 07 29 SR_CH03_AB007EG_01 ...
Страница 34: ......
Страница 95: ...4 CONTROL AND FUNCTIONS 2020 07 29 SR_CH04_AB007EG_01 ...
Страница 97: ...8 8 High temperature and high pressure release control 04 29 CONTENTS continued ...
Страница 98: ......
Страница 129: ...5 FILED WORKING 2020 07 29 SR_CH05_AB007EG_01 ...