Inverter Error
YES
NO
OK
NO
Check Point 1-2 : Noise, momentary open, voltage drop
Inverter PCB
Error information received from Inverter PCB.
1. Noise, momentary open, voltage drop.
2. Power supply to Filter PCB (INV) to Inverter PCB wiring disconnection, open
3. Main PCB to Inverter PCB wiring disconnection, open
4. Magnetic Relay (for inverter) coil side wiring disconnection, open
5. Magnetic Relay activation circuit defective
6. Main PCB or Filter PCB (INV) or Inverter PCB defective
7. Cement Resistor Open circuit
Check if temporary voltage drop was not generated.
Check if momentary open was not generated.
Check if ground is connection correctly
or there are no related cables near the power line.
Check Point 3 : Check the wiring (Power supply to Filter PCB (INV) to Inverter PCB)
Connector and wiring connection state check
Cable open check
Check resistance of cement resistor
Check Point 1-1 : Turn the power on again
Error displayed again?
Indoor Unit : Operation LED 9 times Flash, Timer LED 15 Times Flash,
Filter LED Continuous Flash.
Outdoor Unit : E. 6 3. 1
Error Code : 9 U / 6 3
Trouble shooting 31 E63. 1
Indicate or Display:
Detective Actuators:
Detective details:
OUTDOOR UNIT Error Method:
Forecast of Cause :
Check Filter PCB (INV) and Inverter PCB.
(Refer to "Service Parts Information 3, 4".)
If the circuit of both terminal was open circuit, exchange the Resistor
Correct resistance value: 5.3 - 6.0 Ohm
When "Inverter PCB short interruption detection" or "Rush current limiting
resistor temp. rise protection" occurs, Inverter error also occurs.
YES
Check Point 2 : Check error display
"Inverter PCB short interruption detection" or
"Rush current limiting resistor temp. rise protection" also occur?
In case of "Inverter PCB short interruption detection",
Refer to the Trouble shooting 33.
In case of "Rush current limiting resistor temp. rise protection",
Refer to the Trouble shooting 34.
Check Point 4 : Check the wiring (Main PCB to Inverter PCB)
Connector and wiring connection state check
Cable open check
OK
OK
Check Point 5 : Check Cement resistor
Check Point 6 : Check Filter PCB (INV) and Inverter PCB
Caution
By changing of DIP SW 4-2 to ON, the Back-up operation can start when the active outdoor unit exists on the multi outdoor unit connection.
(Stand alone outdoor unit is impossible)
The following conditions will be concerned in use of back-up operation. (Please do not use the system with back-up operation for long time.)
- The operating compressor life time becomes shorter.
- The operating performance may drop due to the limited active compressor(s).
- The compressor may stop frequently by protection controlling.
*In order to keep the operating capacity, the release of the Low noise mode setting might be necessary.
04-43
Содержание AB* A12GATH
Страница 5: ...1 TEST RUN ...
Страница 28: ...2 OUTDOOR UNIT OPERATION CONTROL ...
Страница 52: ...3 INDOOR UNIT OPERATION ...
Страница 75: ...4 TROUBLE SHOOTING ...
Страница 203: ...5 APPENDING DATA UNIT ...
Страница 207: ...05 04 CASSETTE TYPE MODELS AUXD18GA H AUXD24GA H AUXA18GALH AUXA24GALH AUXA30GA H AUXA36GA H AUXA45GA H AUXA54GA H ...
Страница 208: ...05 05 LOW STATIC PRESSURE DUCT CONCEALED FLOOR TYPE MODEL ARXB07GALH ARXB09GALH ARXB12GALH ARXB14GALH ARXB18GALH ...
Страница 210: ...05 07 LOW STATIC PRESSURE DUCT TYPE MODEL ARXB24GALH ARXB30GALH ARXB36GALH MODEL ARXB45GALH ...
Страница 212: ...05 09 HIGH STATIC PRESSURE DUCT TYPE MODELS ARXC36GATH ARXC45GATH ARXC60GATH MODELS ARXC72GATH ARXC90GATH ...
Страница 213: ...05 10 MODEL ARXC36GBTH MODELS ARXC72GBTH ARXC90GBTH ...
Страница 214: ...FLOOR CEILING TYPE MODELS AB A12GATH AB A14GATH AB A18GATH AB A24GATH 05 11 ...
Страница 215: ...CEILING TYPE MODELS AB A30GATH AB A36GATH AB A45GATH AB A54GATH 05 12 ...
Страница 216: ...05 13 WALL MOUNTED TYPE EEV external model MODELS AS E04GACH AS E07GACH AS E09GACH AS E12GACH AS E14GACH ...
Страница 217: ...05 14 WALL MOUNTED TYPE MODELS AS A04GACH AS A07GA H AS A09GA H AS A12GA H AS A14GA H ...
Страница 218: ...05 15 MODELS AS A18GA H AS A24GA H AS A30GA H ...
Страница 219: ...05 16 MODEL ARXH054GTAH OUTDOOR AIR UNIT MODEL ARXH072GTAH ...
Страница 220: ...05 17 MODEL ARXH096GTAH ...
Страница 221: ...MODELS AJ 072LALBH AJ 090LALBH AJ 072LATBH AJ 090LATBH 05 18 5 2 2 Outdoor Unit ...
Страница 222: ...MODELS AJ 108LALBH AJ 126LALBH AJ 144LALBH AJ 162LALBH AJ 108LATBH AJ 126LATBH AJ 144LATBH AJ 162LATBH 05 19 ...
Страница 225: ...6 DISASSEMBLY PROCESS ...
Страница 226: ......