Communication Error Between
Outdoor unit
OK
OK
Check the number setting of outdoor units.
OK
OK
Outdoor unit Main PCB
1. Noise, momentary open, voltage drop 2. Power supply defective
3. The number setting mistake of outdoor unit
4. Connection of communication lines between outdoor units defective 5. Main PCB defective
Check Point 1 : Noise, momentary open, voltage drop
Check if temporary voltage drop was not generated.
Check if momentary open was not generated.
Check if ground is connection correctly or there are no related cables near the power line.
Check Point 2 : Check the power supply
Main power ON/OFF state check
Power cable connection, open check
Check Point 3 : Check the number setting of outdoor units
Connection and open check of communication lines between outdoor units.
Check Point 4 : Check the connection of communication lines
between outdoor units
Master unit: State in which "number of connected slave units" by Dip-SW and
the number of slave units which can be recognized by
communication did not match continued for 10 seconds or more
after the start of control.
Slave unit: State in which communication from the master unit was not
received continued for 10 seconds or more after the start of control.
Check Point 5 : Replace Main PCB
Change Main PCB and set up the original address.
Outdoor Unit : E. 1 3. 1
Error Code : 9 U / 1 3
Trouble shooting 4 E
1 3. 1
Indicate or Display:
Detective Actuators:
Detective details:
OUTDOOR UNIT Error Method:
Forecast of Cause :
Indoor Unit : Operation LED 9 times Flash, Timer LED 15 Times Flash,
Filter LED Continuous Flash.
Turn off the power and check.
Number of outdoor unit
DIP-SW
SET 5-1
DIP-SW
SET 5-2
1 unit
2 units
3 units
OFF
OFF
ON
OFF
ON
OFF
04-13
Содержание AB* A12GATH
Страница 5: ...1 TEST RUN ...
Страница 28: ...2 OUTDOOR UNIT OPERATION CONTROL ...
Страница 52: ...3 INDOOR UNIT OPERATION ...
Страница 75: ...4 TROUBLE SHOOTING ...
Страница 203: ...5 APPENDING DATA UNIT ...
Страница 207: ...05 04 CASSETTE TYPE MODELS AUXD18GA H AUXD24GA H AUXA18GALH AUXA24GALH AUXA30GA H AUXA36GA H AUXA45GA H AUXA54GA H ...
Страница 208: ...05 05 LOW STATIC PRESSURE DUCT CONCEALED FLOOR TYPE MODEL ARXB07GALH ARXB09GALH ARXB12GALH ARXB14GALH ARXB18GALH ...
Страница 210: ...05 07 LOW STATIC PRESSURE DUCT TYPE MODEL ARXB24GALH ARXB30GALH ARXB36GALH MODEL ARXB45GALH ...
Страница 212: ...05 09 HIGH STATIC PRESSURE DUCT TYPE MODELS ARXC36GATH ARXC45GATH ARXC60GATH MODELS ARXC72GATH ARXC90GATH ...
Страница 213: ...05 10 MODEL ARXC36GBTH MODELS ARXC72GBTH ARXC90GBTH ...
Страница 214: ...FLOOR CEILING TYPE MODELS AB A12GATH AB A14GATH AB A18GATH AB A24GATH 05 11 ...
Страница 215: ...CEILING TYPE MODELS AB A30GATH AB A36GATH AB A45GATH AB A54GATH 05 12 ...
Страница 216: ...05 13 WALL MOUNTED TYPE EEV external model MODELS AS E04GACH AS E07GACH AS E09GACH AS E12GACH AS E14GACH ...
Страница 217: ...05 14 WALL MOUNTED TYPE MODELS AS A04GACH AS A07GA H AS A09GA H AS A12GA H AS A14GA H ...
Страница 218: ...05 15 MODELS AS A18GA H AS A24GA H AS A30GA H ...
Страница 219: ...05 16 MODEL ARXH054GTAH OUTDOOR AIR UNIT MODEL ARXH072GTAH ...
Страница 220: ...05 17 MODEL ARXH096GTAH ...
Страница 221: ...MODELS AJ 072LALBH AJ 090LALBH AJ 072LATBH AJ 090LATBH 05 18 5 2 2 Outdoor Unit ...
Страница 222: ...MODELS AJ 108LALBH AJ 126LALBH AJ 144LALBH AJ 162LALBH AJ 108LATBH AJ 126LATBH AJ 144LATBH AJ 162LATBH 05 19 ...
Страница 225: ...6 DISASSEMBLY PROCESS ...
Страница 226: ......