Cooling operation
An example for COOLING TEMPERATURE CONTROL time chart
When using the cooling mode, set the temperature to a value lower than the target controlling temperature, otherwise
the External refrigeration cycle equipment will not start the cooling operation.
• Indoor fan*
• Opening of
EEV
100%
0%
• Refrigerant
flow
ON
OFF
ON
OFF
• Temperature Ts
T
R
3Min.
Ts+0.5°C: The threshold temperature of start of refrigerant flow
Ts -0.5°C: The threshold temperature of stop of refrigerant flow
(1) When using the heating mode, set the temperature to a value higher than the current room temperature,
otherwise the indoor unit will not start the heating operation.
(2) After the start of heating operation, the fan of indoor unit will not rotate until the heater exchange is warmed up to
blow out warm air.
(3) During defrosting, the OPERATION indicator lamp flashes 6sec. ON and 2sec.OFF, and repeat.
The heating operation will be temporarily interrupted.
An example for HEATING TEMPERATURE CONTROL time chart
T
R
Ts : Corrected Setting temperature : Duration of cold air prevention
TR : Target controlling temperature (Air intake temperature or Air discharge temperature)
TR: Target controlling temperature (Air intake temperature or Air discharge temperature)
Ts : Corrected Setting temperature
+ 0.5°C: Air intake ctrl
+ 0.5°C: Air discharge ctrl
-
0.5°C: Air intake ctrl
-
0.5°C: Air discharge ctrl
Ts
Ts
• Indoor fan*
• Opening of
EEV
100%
0%
• Refrigerant
flow
ON
OFF
ON
OFF
• Temperature Ts
+ 0.5°C: Air intake ctrl
+ 0.5°C: Air discharge ctrl
-
0.5°C: Air intake ctrl
-
0.5°C: Air discharge ctrl
Ts
Ts
Air intake temp controlling
Ts+0.5°C: The threshold temperature of stop of refrigerant flow
Ts -0.5°C: The threshold temperature of stop of refrigerant flow
Air discharge temp controlling
Ts -0.5°C: The threshold temperature of start of refrigerant flow
Ts+0.5°C: The threshold temperature of stop of refrigerant flow
Air intake temp controlling
Ts -0.5°C: The threshold temperature of stop of refrigerant flow
Ts+0.5°C: The threshold temperature of stop of refrigerant flow
*When the EEV operates with the minimum pulse, and it keeps for 5 minutes.
Air discharge temp controlling
Heating operation
3-7-3 FUNDAMENTAL FUNCTIONS
03-20
Содержание AB* A12GATH
Страница 5: ...1 TEST RUN ...
Страница 28: ...2 OUTDOOR UNIT OPERATION CONTROL ...
Страница 52: ...3 INDOOR UNIT OPERATION ...
Страница 75: ...4 TROUBLE SHOOTING ...
Страница 203: ...5 APPENDING DATA UNIT ...
Страница 207: ...05 04 CASSETTE TYPE MODELS AUXD18GA H AUXD24GA H AUXA18GALH AUXA24GALH AUXA30GA H AUXA36GA H AUXA45GA H AUXA54GA H ...
Страница 208: ...05 05 LOW STATIC PRESSURE DUCT CONCEALED FLOOR TYPE MODEL ARXB07GALH ARXB09GALH ARXB12GALH ARXB14GALH ARXB18GALH ...
Страница 210: ...05 07 LOW STATIC PRESSURE DUCT TYPE MODEL ARXB24GALH ARXB30GALH ARXB36GALH MODEL ARXB45GALH ...
Страница 212: ...05 09 HIGH STATIC PRESSURE DUCT TYPE MODELS ARXC36GATH ARXC45GATH ARXC60GATH MODELS ARXC72GATH ARXC90GATH ...
Страница 213: ...05 10 MODEL ARXC36GBTH MODELS ARXC72GBTH ARXC90GBTH ...
Страница 214: ...FLOOR CEILING TYPE MODELS AB A12GATH AB A14GATH AB A18GATH AB A24GATH 05 11 ...
Страница 215: ...CEILING TYPE MODELS AB A30GATH AB A36GATH AB A45GATH AB A54GATH 05 12 ...
Страница 216: ...05 13 WALL MOUNTED TYPE EEV external model MODELS AS E04GACH AS E07GACH AS E09GACH AS E12GACH AS E14GACH ...
Страница 217: ...05 14 WALL MOUNTED TYPE MODELS AS A04GACH AS A07GA H AS A09GA H AS A12GA H AS A14GA H ...
Страница 218: ...05 15 MODELS AS A18GA H AS A24GA H AS A30GA H ...
Страница 219: ...05 16 MODEL ARXH054GTAH OUTDOOR AIR UNIT MODEL ARXH072GTAH ...
Страница 220: ...05 17 MODEL ARXH096GTAH ...
Страница 221: ...MODELS AJ 072LALBH AJ 090LALBH AJ 072LATBH AJ 090LATBH 05 18 5 2 2 Outdoor Unit ...
Страница 222: ...MODELS AJ 108LALBH AJ 126LALBH AJ 144LALBH AJ 162LALBH AJ 108LATBH AJ 126LATBH AJ 144LATBH AJ 162LATBH 05 19 ...
Страница 225: ...6 DISASSEMBLY PROCESS ...
Страница 226: ......