Trouble shooting 81
E39. 1
INDOOR UNITError Method:
Indoor Unit power supply error for
FAN motor 1 (2)
Indicate or Display:
Outdoor Unit :E.5 U.1
Error Code :39, 39.1(2)
Detective Actuators:
Indoor Unit Controller PCB Circuit
Indoor Unit Power supply PCB Circuit
Detective details:
When the DC power input for Fan motor < W500 - W501 (W530 - W531) on
the Power supply PCB > becomes lower voltage than the specified voltage.
Check Point 2 : Check wire connection
Wire lose connection / damage between the CN21 on the Controller PCB and CN250 on the Power supply PCB.
In case of Model 72, between W530 (W531) on the Power supply PCB and Capacitor.
>>If there is abnormal on the wire, replace it
OK
Forecast of Cause :
1. Noise momentary open, voltage drop 2. Wire connection 3. Fan motor
4. Peripheral electric devices 5. Power supply PCB 6. Controller PCB
04-90
(E39. 2)
Check Point 1 : Check if any outside cause such as voltage drop or noise
Instant voltage drop ----------- Check if there is any electric equipment with a large load within the same circuit
.
Momentary power failure ---- Check contact failure or leak current in power supply circuit
Check if there is any equipment that causes harmonic wave near the power cable
(Neon light bulb or any electronic equipment whichcauses harmonic wave). And check the complete insulation of grounding.
>>If the same symptom does not reappear after resetting the power, possibility of noise is high.
OK
Check Point 3 : Check rotation of Fan / wire resistance
Rotate the applicable fan by hand when operation is off.
OK
Disconnect the connector from the Power supply PCB and Check resistance value of Motor connector.
(Refer to the service parts information 20)
Check Point 4 : Check peripheral devices, Posistor, Capacitor, Diode bridge
Check resistance value, short circuit, visible damage
>>If there is abnormal , replace it
Check Point 5 : Replace Power supply PCB
Change Power supply PCB
Check Point 6 : Replace Controller PCB
Change Controller PCB and set up the original address.
OK
NG
Содержание AB* A12GATH
Страница 5: ...1 TEST RUN ...
Страница 28: ...2 OUTDOOR UNIT OPERATION CONTROL ...
Страница 52: ...3 INDOOR UNIT OPERATION ...
Страница 75: ...4 TROUBLE SHOOTING ...
Страница 203: ...5 APPENDING DATA UNIT ...
Страница 207: ...05 04 CASSETTE TYPE MODELS AUXD18GA H AUXD24GA H AUXA18GALH AUXA24GALH AUXA30GA H AUXA36GA H AUXA45GA H AUXA54GA H ...
Страница 208: ...05 05 LOW STATIC PRESSURE DUCT CONCEALED FLOOR TYPE MODEL ARXB07GALH ARXB09GALH ARXB12GALH ARXB14GALH ARXB18GALH ...
Страница 210: ...05 07 LOW STATIC PRESSURE DUCT TYPE MODEL ARXB24GALH ARXB30GALH ARXB36GALH MODEL ARXB45GALH ...
Страница 212: ...05 09 HIGH STATIC PRESSURE DUCT TYPE MODELS ARXC36GATH ARXC45GATH ARXC60GATH MODELS ARXC72GATH ARXC90GATH ...
Страница 213: ...05 10 MODEL ARXC36GBTH MODELS ARXC72GBTH ARXC90GBTH ...
Страница 214: ...FLOOR CEILING TYPE MODELS AB A12GATH AB A14GATH AB A18GATH AB A24GATH 05 11 ...
Страница 215: ...CEILING TYPE MODELS AB A30GATH AB A36GATH AB A45GATH AB A54GATH 05 12 ...
Страница 216: ...05 13 WALL MOUNTED TYPE EEV external model MODELS AS E04GACH AS E07GACH AS E09GACH AS E12GACH AS E14GACH ...
Страница 217: ...05 14 WALL MOUNTED TYPE MODELS AS A04GACH AS A07GA H AS A09GA H AS A12GA H AS A14GA H ...
Страница 218: ...05 15 MODELS AS A18GA H AS A24GA H AS A30GA H ...
Страница 219: ...05 16 MODEL ARXH054GTAH OUTDOOR AIR UNIT MODEL ARXH072GTAH ...
Страница 220: ...05 17 MODEL ARXH096GTAH ...
Страница 221: ...MODELS AJ 072LALBH AJ 090LALBH AJ 072LATBH AJ 090LATBH 05 18 5 2 2 Outdoor Unit ...
Страница 222: ...MODELS AJ 108LALBH AJ 126LALBH AJ 144LALBH AJ 162LALBH AJ 108LATBH AJ 126LATBH AJ 144LATBH AJ 162LATBH 05 19 ...
Страница 225: ...6 DISASSEMBLY PROCESS ...
Страница 226: ......