01-06
Check Item
Check contents
Judgement
Present Status
Number of ref. circuit connected in the network system : ______, Ref. addresses :_______ _______________(00 99)
VRF
Network
System
Network
Configuration
No. of IUs & OUs
For one VRF Network System
(IU 400 & OU 100)
IU number : _____
OU number: _____
No. of System Controller
One System Controller per VRF Network System
No. of Touch panel controller (TPC)
Connectable Nos. 16
Total 16 Nos.
Per VRF Network System
(including one Network
Converter for LonWorks)
TPC: _____
No. of Central RC (CRC)
Connectable Nos. 16
CRC: ______
No. of Network Convert for Group RC
Connectable Nos. 64
Group RC: _____
No. of Signal Amplifier (SA) 40
Detail contents:
No. of SA (filter mode OFF) 8
No. of SA (filter mode ON ) 32
One per 500m transmission line length OR,
One per 400m transmission line length between
units OR,
One per every 64 number of connected units OR,
One per every master OU if total number of
connected Indoor Units 320
Number of Signal
Amplifier :________
No. of Network Convertor ( 100)
One for each separate Room Air
- conditioning system
Total:_______
No. of BACnet Gateway
One BACnet Gateway per VRF Network System
Total: _______
Terminal Register
One per Network Segment (refer to table -9)
Total: _______
No. of Network Convertor for LonWorks
One per VRF Network System (IU 128 & OU 100)
NOTE: Special VRF Network system configuration
IU number : _____
OU number: _____
Check Item
Check contents
Judgement
Present Status
Number of ref. circuit connected in the network system : ______, Ref. addresses :_______________________(00 99)
VRF
Network
System
Terminal
Resistance of
transmission
line
Terminal resistance of transmission line:
From device with connected terminal
resistance (OU or SA) to the most
distance device
50 ohm ( Resistance value) 180 ohm
OK / Not OK
In- between
OU (add____) & SA (add___)
OK / Not OK
In- between
SA (add____)
OK / Not OK
In- between
OU (add____) & SA (add___)
1-2-4 Transmission wire installation inspection sheet 3/3
Distance from termination resistor (m)
0 ~100
~ 200
~ 300
~400
~500
Approximate
resistance
(
Ω
)
0 ~ 50
A short circuit somewhere or 2 or more termination
resistors are connected
50
60
70
80
90
100
110
120
130
140
150
160
170
180
190 ~
Faulty contact or wiring length over 500 m
1K ~
∞
Faulty contact, open circuit, or no termination resistor
Содержание AB* A12GATH
Страница 5: ...1 TEST RUN ...
Страница 28: ...2 OUTDOOR UNIT OPERATION CONTROL ...
Страница 52: ...3 INDOOR UNIT OPERATION ...
Страница 75: ...4 TROUBLE SHOOTING ...
Страница 203: ...5 APPENDING DATA UNIT ...
Страница 207: ...05 04 CASSETTE TYPE MODELS AUXD18GA H AUXD24GA H AUXA18GALH AUXA24GALH AUXA30GA H AUXA36GA H AUXA45GA H AUXA54GA H ...
Страница 208: ...05 05 LOW STATIC PRESSURE DUCT CONCEALED FLOOR TYPE MODEL ARXB07GALH ARXB09GALH ARXB12GALH ARXB14GALH ARXB18GALH ...
Страница 210: ...05 07 LOW STATIC PRESSURE DUCT TYPE MODEL ARXB24GALH ARXB30GALH ARXB36GALH MODEL ARXB45GALH ...
Страница 212: ...05 09 HIGH STATIC PRESSURE DUCT TYPE MODELS ARXC36GATH ARXC45GATH ARXC60GATH MODELS ARXC72GATH ARXC90GATH ...
Страница 213: ...05 10 MODEL ARXC36GBTH MODELS ARXC72GBTH ARXC90GBTH ...
Страница 214: ...FLOOR CEILING TYPE MODELS AB A12GATH AB A14GATH AB A18GATH AB A24GATH 05 11 ...
Страница 215: ...CEILING TYPE MODELS AB A30GATH AB A36GATH AB A45GATH AB A54GATH 05 12 ...
Страница 216: ...05 13 WALL MOUNTED TYPE EEV external model MODELS AS E04GACH AS E07GACH AS E09GACH AS E12GACH AS E14GACH ...
Страница 217: ...05 14 WALL MOUNTED TYPE MODELS AS A04GACH AS A07GA H AS A09GA H AS A12GA H AS A14GA H ...
Страница 218: ...05 15 MODELS AS A18GA H AS A24GA H AS A30GA H ...
Страница 219: ...05 16 MODEL ARXH054GTAH OUTDOOR AIR UNIT MODEL ARXH072GTAH ...
Страница 220: ...05 17 MODEL ARXH096GTAH ...
Страница 221: ...MODELS AJ 072LALBH AJ 090LALBH AJ 072LATBH AJ 090LATBH 05 18 5 2 2 Outdoor Unit ...
Страница 222: ...MODELS AJ 108LALBH AJ 126LALBH AJ 144LALBH AJ 162LALBH AJ 108LATBH AJ 126LATBH AJ 144LATBH AJ 162LATBH 05 19 ...
Страница 225: ...6 DISASSEMBLY PROCESS ...
Страница 226: ......