(3) Position preset (
)
The current position of motor can be preset. The following alarm detection can be reset.
・
ABS data loss
Current position is the followings :
(a) [D14] to [D0] input value for RYS
□□□
S3-RPS type
(b) Station No. of 8, 9 word position for RYS
□□□
-RSS type
(c) Station No. of +6, +7 word position for RYS
□□□
S3-RTS type
Position preset cannot be made while the motor is rotating and while on status of the clamping end signal.
(4) Alarm reset (
)
Resets the alarm detected by the amplifier.
(5) History initialization (
)
Deletes the history of alarms detected held by the amplifier.
This history can be monitored by a sequence mode of [
].
The alarm history is held even after turning off power.
(6) Parameter initialization (
)
Initializes the basic para. and system para.
* After initializing, be sure to turn off and on power.
ENT (1 [s] or more)
ESC
ENT
ESC
ENT
ENT (1 [s] or more)
ESC
ENT
ESC
(Initializing end)
(Initializing end)
ENT
ENT (1 [s] or more)
ESC
ESC
ESC
ENT (1 [s] or more)
ESC
Preset end
ESC
ENT
Содержание Faldic-a RYS-R Series
Страница 1: ...RYS R Type User s Manual MHT260a Engl...
Страница 2: ...0...
Страница 78: ...0...
Страница 79: ...0 1 1 1 23 1 4 5 6 1 7 8 1 2 8 1 1 1 1 1 1 1 1 9 9 9 9 9 0 1 9 1 9 1 9 1 9 1 9 1...
Страница 81: ...0 1 20 3 4 2 20 5 20 5 4 2 3 4 4 6 4 72 4 7 4...
Страница 83: ...0 0 0 0 0 0 1 1 2 3 4 0 1 0 5 6 1 0 6 7 0 0 8 0 9 5 5 2 9 0 6 4 5 5 2 3 9 7 9 7 9 5 5 4 6 6...
Страница 84: ...6 7 A 6 B C D5 7 4 4 6 4 5 1 BE8 F70 CPU...
Страница 85: ...0 1 2 3 4 3 3 3 5 1 678...
Страница 86: ...0 1 1 0 1 2 2 3 4 5 4 5 2 1 678 4 9 95 9 9 1 9 1 3 3 1 4 5 06 2 3 0 06 4 4 0 0 0 0 0 3 4 0...
Страница 87: ...0 0 0 A A 0 0 0 0 0 0...