MHT260a (Engl.)
5-8
(6) Non-linear (S-curve) acceleration/deceleration
S-curve accel./decel. can be carried out by basic para. 25 setting.
The speed slowly increases by drawing an S-curve, and a mechanical shock during acceleration can be reduced.
(7) Manual indexing
The stop position when the [FWD] signal is off depends on the setting of basic para. 81.
Basic parameter 81
Setting range
Stop position
0: Shortest
Stops at the shortest station with the preset decel. time.
1: Invalid
Decelerates and stops when the forward (reverse) command is
off. Does not stop at the station position.
2: Station No.
Stops at the station number position at the ON edge of the
forward (reverse) command.
Note: To stop at the station, origin return action (or equivalent) must have been completed.
1:Invalid
Speed
Ready
Forward command [FWD]
Time
ON
ON
OFF
Indexing end
(
level
)
ON
OFF
Stop position
Speed
Manual forward
OFF
Speed
Ready
Forward command [FWD]
Time
ON
ON
OFF
D14
to
D0
07
02
Indexing end
(
level
)
ON
OFF
ON
Stop position
Speed
Manual forward
0 : Shortest/2 : Station No.
OFF
Содержание Faldic-a RYS-R Series
Страница 1: ...RYS R Type User s Manual MHT260a Engl...
Страница 2: ...0...
Страница 78: ...0...
Страница 79: ...0 1 1 1 23 1 4 5 6 1 7 8 1 2 8 1 1 1 1 1 1 1 1 9 9 9 9 9 0 1 9 1 9 1 9 1 9 1 9 1...
Страница 81: ...0 1 20 3 4 2 20 5 20 5 4 2 3 4 4 6 4 72 4 7 4...
Страница 83: ...0 0 0 0 0 0 1 1 2 3 4 0 1 0 5 6 1 0 6 7 0 0 8 0 9 5 5 2 9 0 6 4 5 5 2 3 9 7 9 7 9 5 5 4 6 6...
Страница 84: ...6 7 A 6 B C D5 7 4 4 6 4 5 1 BE8 F70 CPU...
Страница 85: ...0 1 2 3 4 3 3 3 5 1 678...
Страница 86: ...0 1 1 0 1 2 2 3 4 5 4 5 2 1 678 4 9 95 9 9 1 9 1 3 3 1 4 5 06 2 3 0 06 4 4 0 0 0 0 0 3 4 0...
Страница 87: ...0 0 0 A A 0 0 0 0 0 0...