![FRIEDLAND SA3 PLUS Скачать руководство пользователя страница 16](http://html1.mh-extra.com/html/friedland/sa3-plus/sa3-plus_installation-and-operating-manual_2332728016.webp)
parallel gap between the Magnet and Detector
is less than 10mm and that the arrow on the
Magnet is pointing towards and aligned with the
mark on the top section of the Detector.
5. If an additional wired Magnetic Contact is
required, this should be wired to the terminal
block provided in the battery compartment. The
wired contact should be connected using two
core (24AWG) wire of maximum length 1.5m.
If an additional wired contact is connected to the
Detector then jumper link S2 on the PCB must
be removed.
IMPORTANT: If an additional wired contact is
not connected, then the jumper link SW2 must
be fitted for the detector to operate correctly.
6. Configure the House Code for the Magnetic
Contact Detector by setting DIP switches 1-8 to
the same ON/OFF combination as the House
Code DIP switches in all other system devices.
7. Configure the alarm zone which the detector will
operate on with DIP switches 9-11 as follows:
DIP 9
DIP 10
DIP 11
Zone 1
OFF
OFF
OFF
Zone 2
OFF
OFF
ON
Zone 3
OFF
ON
OFF
Zone 4
OFF
ON
ON
Zone 5
ON
OFF
OFF
Zone 6
ON
OFF
ON
8. Slide the batteries supplied into the battery holder,
ensuring that the positive (+) side is uppermost on
each battery as it is installed.
9. Carefully refit the battery holder onto the Detector
ensuring that the spring connectors slide onto
either side of the circuit board.
10. Fit the battery cover into position on the Detector.
TESTING THE MAGNETIC CONTACT
DETECTORS
Ensure that the system is in Test mode, (see page 18).
1. Put the Control Panel into "Walk Test" mode by
pressing on the Control Panel.
The Panel will beep and the Zone 1 LED will illuminate.
2. Remove the battery cover from the Detector.
The LED on the Detector will illuminate for approx.
1s as the battery cover is removed and the tamper
switch is activated. In addition, the Control Panel
will beep twice to indicate that the alarm signal has
been received and the Tamper LED will illuminate.
3. Open the door/window to remove the magnet from
the Detector.
As the magnet is moved away from the detector
the LED will illuminate for approximately 1s to
indicate that the Detector has been triggered. In
addition, the Control Panel will beep twice to
indicate that the alarm signal has been received
and the appropriate zone LED, which the detector
is configured for, will illuminate.
4. If any external Magnetic Contact Sets are
connected to the Detector, operate these one at a
time. Each time a contact is opened the LED on
the Detector should illuminate for 1s to indicate
that it has been triggered.
14
(Ensure back
surfaces are flush)
Detector
Magnet
Alternative
Mounting
House Code
Location of
Key-hole Screw
(underside)
Hole for
Mounting
Screw
Zone
Terminal Block for Additional
Wired Magnetic Contact
Jumper
Link S2
Anti-Tamper
Switch
1