5100ex Calibration Manual
AutoCalibration of Direct Liquid
44
STEP 13: Measure the amount of liquid that was dispensed and enter the value. The
process will have to be started over if less than 2 gallons were dispensed.
STEP 14: Press Next to continue. The Full Speed Displacement Rate screen will appear.
It will be populated with the value calculated by the 5100ex. You can adjust this
value if necessary using the arrow keys. This value will only be correct if you
have a positive displacement pump or set the output to 100% during STEP 7:
STEP 15: If your system is an open loop system skip to step STEP 17:.
STEP 16: Press Next to continue. The Displacement screen will appear populated with the
value calculated by the 5100ex. You can adjust this value if necessary using the
arrow keys.
STEP 17: Press Done. AutoCal is complete and you will be returned to the menu you
entered from.
STEP 18: Repeat the above steps for each Direct Liquid material type that is enabled.