5100ex Calibration Manual
AutoCalibration of Granular Materials
34
STEP 14: Weigh the amount of material that was dispensed and enter the value. The
process will have to be started over if less than 25 LBS were dispensed.
STEP 15: Press Next to continue. The Full Speed Displacement Rate screen will appear.
It will be populated with the value calculated by the 5100ex. You can adjust this
value if necessary using the arrow keys.
STEP 16: If your system is an open loop system skip to step STEP 18:.
STEP 17: Press Next to continue. The Displacement screen will appear populated with the
value calculated by the 5100ex. You can adjust this value if necessary using the
arrow keys.
STEP 18: Press Done. AutoCal is complete and you will be returned to the menu you
entered from.