5100ex Calibration Manual
Description of Calibration Values
7
Blast Time
The Blast Time menu item sets the amount of time in seconds that blast will run
once the blue Blast Knob has been pressed and released. The default value is
10 seconds.
Manual Mode
The Manual Mode menu item enables or disables the Manual mode switch on
the Operation Screen. When operated in Manual mode, the 5100ex ignores any
connected auger feedback sensor and vehicle ground speed and will instead
drive the auger output at a fixed percent of maximum speed. The default value is
disabled.
Unload
The Unload menu item enables unload mode for all granular materials in the
Unload/Prime menu. The default value is disabled.
Low Material
The Low Material menu item determines what spreader action is triggered when
the Low Material input becomes active. The available options are Warn or Warn
+ No Log. The default value is Warn.
Function
Operation
Warn
The Low Material error will appear in the header bar.
Warn + No Log
The low material error will appear in the header bar and the
granular material totals will stop updating.
Aug Rev Valve
The Auger Reverse Valve Type menu item determines the operation of the Auger
Forward and Auger Reverse outputs, depending on the type of valve installed in
the system. This menu item is disabled in 5150 mode. The default value is None.
Option
Description
None
For systems with no Auger Reverse output
Proportional
For systems with two proportional valves, one for Auger
Forward and one for Auger Reverse
Selector
For systems with one proportional valve used for Auger
Forward and Auger Reverse, and an external selector valve
to determine which output is run
Reverse
The Reverse menu item enables Auger Reverse mode and the Auger Reverse
switch on the Operation Screen. The default value is disabled. The Reverse
button is disabled in 5150 systems.
If the system is not equipped with a 9F harness, Auger Reverse mode will not run
an output.
Clear Jam
The Clear Jam menu item enables Clear Jam and the Clear Jam switch on the
Operation Screen. The default value is disabled. The Clear Jam button is
disabled in 5150 systems.
If the system is not equipped with a 9F harness, Auger Reverse mode will not run
an output.