31
4.6.2. Ø 80 mm air intake/flue gas discharge via split ducts
The information given is with reference to air intake/flue gas discharge ducts made from smooth, rigid pipes approved and
supplied by the manufacturer.
Installation types C43 - C53 - C83
KC 24
Minimum permissible length of air intake duct is 1 meter.
Minimum permissible length of flue gas discharge duct is 1 meter.
Maximum permissible length of air intake/flue gas discharge ducts is 84 meters (combined length of air intake and flue gas discharge pipe
length).
For each additional 1 meter of straight duct maximum permissible length is to be reduced by 1 meter.
For each additional 90° elbow, maximum permissible length is to be reduced by 1 meter.
For each additional 45° elbow, maximum permissible length is to be reduced by 0.5 meter.
The roof terminal reduces maximum permissible length by 5.5 meters.
The wall terminal reduces maximum permissible length by 5 meters.
KC 28
Minimum permissible length of air intake duct is 1 meter.
Minimum permissible length of flue gas discharge duct is 1 meter.
Maximum permissible length of air intake/flue gas discharge ducts is 91 meters (combined length of air intake and flue gas discharge pipe
length).
For each additional 1 meter of straight duct maximum permissible length is to be reduced by 1 meter.
For each additional 90° elbow, maximum permissible length is to be reduced by 1.5 meter.
For each additional 45° elbow, maximum permissible length is to be reduced by 1 meter.
The roof terminal reduces maximum permissible length by 5.5 meters.
The wall terminal reduces maximum permissible length by 5.5 meters.
250
400
700
74
Ø 80
155
152,5
126
fig.15
fig.16
Содержание Antea 24kW Range
Страница 39: ...39 A fig 21...
Страница 51: ...51 1 2 31 32 33 34 fig 31 9 Spare part list...
Страница 52: ...52 4 5 6 7 9 8 10 11 12 13 29 14 15 3 17 18 19 20 21 22 23 24 25 26 27 29 29 30 28 14 16 fig 32...
Страница 56: ...56...
Страница 57: ...57...
Страница 58: ...58 Affix your analyser print out here...
Страница 59: ...59...