Operating Manual CMGZ 622
19
Configuring the Electronic Unit
The use of the input channels provided is as follows:
Input Channel assignment (ref. also to wiring diagram)
CMGZ622
Channel 1
Force Sensor, range 1 (low nominal force)
Channel 2
Force Sensor, range 2 (high nominal force)
Channel 3
External Reference / Diameter / Line Speed
Channel 4
–
Prior to the first calibration, the following settings must be done for each channel (ref.
to „14. Parametrization“ and „19. Technical reference“):
Jumpers for the analog outputs (ref. also to „19. Technical Reference)
CMGZ622
Channel 1
±10V (using a drive) or 0...10V (using a brake)
Channel 2
0...10V (default)
Channel 3
–
Channel 4
–
System parameters
Language
Required display language
Parameters CMGZ622
Nominal force 1
Low nominal force, ref. to nameplate of the force
sensor
Nominal force 2
High nominal force, ref. to nameplate of the force
sensor
Unit of sensor
Ref. to nameplate of the force sensor
Sensitivity
FMS force sensors = 1.8mV/V (default)
1 or 2 sensors
1 or 2 per channel
Lowpass feedback
Reset to default = 50.0 Hz
Scale instrument 1
Which material tension feedback refers to 10V resp.
20mA?
Scale instrument 2
Which material tension feedback refers to 10V resp.
20mA?
These parameters are required to setup the measuring amplifier section of the
electronic unit. There are additional parameters required to setup the PID controller
section (refer to „10. Setup of an Unwind Brake Controller“ / „11. Setup of an Unwind
Drive Controller“ / „12. Setup of a Winding Drive Controller“ / „13. Setup of a Line
Drive Controller“)
Note
Wrong setting of the jumpers and parameters may cause malfunction of the electronic
unit! Setting of the parameters must be done carefully prior to setting into operation!