Operating Manual CMGZ 622
50
Reference source
Applies to:
Unwind brake
Unwind drive
Winding drive
Line drive
Use:
If the reference value will be set using the operating panel or the
interface, this parameter has to be set to
internal
. If the reference
value will be set using a 0...10V signal led to the analog input, this
parameter has to be set to
external
.
Range:
Internal,
External
Default:
Internal
Scale ref. input 1
Applies to:
Unwind brake
Unwind drive
Winding drive
Line drive
Use:
This parameter defines which force value is assigned to a 10 V
signal on the analog reference input if measuring range 1 is used
(digital input „switch range“ = OFF).
Range:
A force value can be input. The value consists of 4 digits. The
position of the decimal point depends on the parameter
Force of
sensor.
Default:
-
Unit:
[N, kN, cN] or [lb, klb, clb]
Scale ref. input 2
Applies to:
Unwind brake
Unwind drive
Winding drive
Line drive
Use:
This parameter defines which force value is assigned to a 10 V
signal on the analog reference input if measuring range 2 is used
(digital input „switch range“ = ON).
Range:
A force value can be input. The value consists of 4 digits. The
position of the decimal point depends on the parameter
Force of
sensor.
Default:
-
Unit:
[N, kN, cN] or [lb, klb, clb]
Torque in use?
Applies to:
Unwind brake
Use:
If this parameter is set to
no
, the output value will be 0V while the
controller is disabled. When enabling the controller, the value set
under parameter
holding torque
will be output. So, the controller
starts from the holding torque value when enabling it.
If this parameter is set to
yes
, the output value will be as defined in
parameter
Holding torque
constantly while the controller is disabled.
So, the controller brakes all the time constantly with the holding
torque while disabled. When enabling the controller, it starts from
the holding torque and returns to the holding torque if the controller
is disabled again.
Range:
Yes,
No
Default:
No