1.8.1 Normal Mode:
Normal mode is the standard mode of operation. In this mode, the UDACT-F
monitors host FACP status as well as monitoring telephone line voltage. The
UDACT-F reports system status information to UL listed Central Stations.
Information transmitted includes general alarm, trouble and supervisory. It also
transmits either the number of zones or points activated or the specific point(s)
activated. Specific system trouble conditions and specific UDACT-F troubles are
also transmitted.
1.8.2 Program Mode:
Program mode is used to program the UDACT-F. While the UDACT-F is in the
program mode, it cannot receive host FACP status information. See Section 3.0 for
complete programming instructions.
1.8.3 Lamp Test Mode:
This mode turns on all segments of the 4 character display plus all LEDs on the
UDACT-F.
1.8.4 Troubleshoot Mode:
Troubleshoot mode may be used for testing the telephone line wiring. Connection
from the UDACT's modular jacks, through RJ31X jacks and into the telephone
network may be easily checked. In this mode, the keypad acts similar to a telephone
touchpad.
1.8.5 Type Mode
Type mode is used to define the specific type of device (point) used or function of a
zone. This mode is also used to disable the alarm report for any zone/point in the
system. The feature which disables the zone/point alarm report must be used for
zones/points programmed into the host FACP as remote silence, reset, drill or
acknowledge switches.
1.8.6 Clear Function:
When the clear function is activated, it causes the UDACT-F to immediately stop
transmissions, hang-up from the telephone network, clear out any messages that
were waiting for transmission and reset.
1.8.7 Manual Test Function:
The manual test function allows for a test report message to be sent to both Central
Stations upon activation.