Appendix A: Reporting Formats
Table A-1 shows the data reporting structure for each of the pulsed formats as well as the Ademco
Express formats. Ademco Express formats allow a typical data message to be transmitted to the
Central Station in under 5 seconds. Pulsed formats typically require 15 to 20 seconds in
comparison. Table A-2 defines each letter code used in Table A-1. Table A-3 describes the data
reporting structure used for Ademco Contact ID format.
Format #
0,2, 4, 6, 8
Format #
1,A, C
Report
3+1/4+1/Standard
4+1 Express
4+2/Standard
4+2 Express
Alarm
SSS(S) A
SSSS AA2
Alarm Restore
SSS(S) RA
SSSS RARA2
Zone Trouble
(Zone Open)
SSS(S) RTZ
SSSS TZTZ2
Zone Trouble Restore
SSS(S) RTZ
SSSS RTZRTZ2
System Trouble
SSS(S) TS
SSSS TSTS2
System Trouble Restore
SSS(S) RTS
SSSS RTSRTS2
Low Battery
SSS(S) L
SSSS LL2
Low Battery Restore
SSS(S) RL
SSSS RLRL2
AC Loss
SSS(S) P
SSSS PP2
AC Loss Restore
SSS(S) RP
SSSS RPRP2
Supervisory Condition
SSS(S) V
SSSS VV2
Supervisory Condition
Restore
SSS(S) RV
SSSS RVRV2
Test Report
SSS(S) X
SSSS XX2
Abnormal Test Report
SSS(S) XA
SSSS XAXA2
Table A-1: Data Reporting Structure
Refer to Table A-2 for an explanation of each letter code in Table A-1.
Refer to Table B-1 for a list of compatible receivers.