19
Document # 50049 Rev D 5/2/97 P/N 50049:D
Caution: Connecting a UDACT-F to a Sensiscan 2000 which also has an AFM or LDM
series annunciator connected will alter the assignments of the first eight yellow LEDs
on the annunciator as follows:
Sensiscan 2000
Yellow Annunciator LED
Assignment
Without UDACT-F
Assignment
With UDACT-F
1
System Trouble
(less AC loss)
System Trouble
(less AC loss)
2
Signals Silenced
Signals Silenced
3
Not Used
Not Used
4
Supervisory
Supervisory
5
Indicating Ckt 1 Trouble
Indicating Ckt 1 Trouble
6
Indicating Ckt 2 Trouble
Indicating Ckt 2 Trouble
7
Municipal Tie Trouble
Low Battery/
Ground Fault
8
AC Fail
AC Fail
Table 2-2: Annunciator LED Assignments - S-2000
Technical Manuals Online! - http://www.tech-man.com